TFP213 <br /> Page 3 of 4 <br /> Sprinkler Spacing al Building Code (IBC) and Internation- <br /> The maximum coverage area per sprin- al Fire Code (IFC) for CMSA sprinklers <br /> kler is 196 ft2 (18,2 m2). The minimum with an RTI of 50 or less and a design WRENCH <br /> coverage area per sprinkler is 100 ft2 of 12 or fewer sprinklers. RECESS <br /> (9,3 m2). The maximum distance be- Construction Type For NFPA 13, <br /> tween sprinklers is 14 ft. (4,3 m). The Chapter 21,—Alternative Systems <br /> minimum distance between sprinklers Designs �, <br /> is 10 ft. (3,05 m). In accordance with NFPA 13 for Ex- �'1 ".Z <br /> Note: When a wall or obstruction tended Coverage Sprinklers for High ` lfg11 <br /> makes a minimum spacing of 10 ft. Piled Storage. <br /> (3,05 m)impossible, consult FM Glob- Obstruction Criteria for NFPA 13 <br /> al Property Loss Prevention Data Chapter 21 —Alternative Systems "FITTING SIDE" O <br /> Sheet 2.0 for applicable guidelines. Design TOWARDS SPRINKLER <br /> Follow Sections 8.8.5.1, (Extended FITTING <br /> Sprinkler Location Coverage Obstruction Guidelines for <br /> Locate sprinklers with respect to the Sprinkler Discharge Pattern Devel- <br /> ceiling/roof ceiling/roof in accordance with FM opment); 8.12.5.2 and 8.12.5.3 (ESFR FIGURE 2 <br /> Global Property Loss Prevention Data Obstruction Criteria for obstruction W-TYPE 1 <br /> Sheet 2.0. that prevent the pattern from reaching SPRINKLER WRENCH <br /> Obstructions the hazard below). <br /> Follow the obstruction requirements . Exception: When using the Up- Step 2. With pipe-thread sealant sp- <br /> as detailed in FM Global Property Loss right EC-25 Sprinkler, any continu- plied, hand-tighten the sprinkler into <br /> Prevention Data Sheet 2.0. ous obstruction 4 inches (100 mm) the sprinkler fitting. Do not apply any <br /> han- <br /> or less shall be permitted to be ig force to the Link Assembly, and Other Details nored in accordance with NFPA 13, dle the Model EC-25 Sprinkler only by <br /> All other design details should be in the Frame arms. <br /> section 21.5.3.2.3. <br /> accordance with FM Global Proper- Step 3. Wrench-tighten the Model <br /> ty Loss Prevention Data Sheet 2.0 as Deflector Distance Below Ceiling EC-25 Sprinkler using only the W-Type <br /> well as any other applicable FM Glob- Follow NFPA 13, Section 8.8.4 for al- 1 Sprinkler Wrench (Figure 2) and by <br /> al Data Sheet. lowed deflector distances below <br /> fully engaging (seating)the wrench on <br /> NFPA 13,CHAPTER 21 ceiling. the sprinkler Wrench Flats. <br /> ALTERNATIVE SYSTEM DESIGN Clearance to Storage Step 4. After installation, inspect the <br /> (CMSA) Minimum 36 inches from deflector to Link Assembly of each Model EC- <br /> The TYCO Model EC-25 Extended top of storage required. 25 Sprinkler for damage. In particu- <br /> Coverage Upright Sprinklers (TY9128) lar, verify that the Link Assembly and <br /> Maximum Distance Between Hook are positioned as illustrated in <br /> have successfully undergone large- Sprinklers Figure 1, and that the Link Assembly <br /> scale fire tests at Factory Mutual to 14 ft. (4,3 m) has not been bent, creased, or forced <br /> comply with Chapter 21 of NFPA 13, out of its normal position in any way. <br /> 2013 Edition. As such, Tables 21.2.2 Minimum Distance Between <br /> and 21.3.2 of NFPA 13 may be utilized Sprinklers Damaged sprinklers must be replaced <br /> for design options with the Model EC- 10 ft. (3,0 m) immediately. <br /> 25 Upright Sprinklers for providing ceil- <br /> ing-only protection. Installation <br /> This allows for the protection of Pal- <br /> letized, Solid Piled, Bin Box, Shelf, or The TYCO Model EC-25 Upright <br /> Back-to-Back Shelf Storage as well as Sprinklers are to be installed in accor- <br /> Single, Double,and Multiple Row Open dance with this section. <br /> Rack protection of up to 30 ft.(9,1 m)of Damage to the fusible Link Assembly <br /> Cartoned Unexpanded Group A Plas- during installation can be avoided by <br /> tic Commodities in a maximum 35 ft. handling the sprinkler using only the <br /> (11 m) ceiling condition with extended frame arms and the appropriate sprin- <br /> spacing up to 196 sq. ft. while main- kler wrench. Do not grip or apply any <br /> taining very reasonable flow and pres- force to the Fusible Link Assembly. <br /> sure requirements. Pipe sizes as well Damaged sprinklers must be replaced <br /> as water supply requirements can now immediately. <br /> be kept to a minimum when compared <br /> to other design methods for high piled A leak-tight 1 inch NPT sprinkler joint <br /> storage challenges. Refer to Tables should be obtained by applying a min- <br /> A and B of this data sheet for specific imum-to-maximum torque of 20 to 30 <br /> flow, pressure, and number of sprin- ft.-lbs. (26,8 to 40,2 Nm). Higher levels <br /> klers to be calculated. of torque may distort the sprinkler in- <br /> When used in accordance with NFPA let with consequent leakage or impair- <br /> Chapter 21, smoke vents and draft ment of the sprinkler. <br /> curtains are not required as specified Step 1. Install the Model EC-25 Sprin- <br /> in the 2015 edition of the Internation- kler in the upright position. <br />