TFP213
<br /> Page 4 of 4
<br /> Storage Commodity Max. Max. Type pe of Number Min. Max. Hose Water
<br /> Arrangement Class Storage Ceiling/ System of Design Operating Coverage Stream Supply
<br /> Height Roof Sprinklers Pressure Area Allowance Duration
<br /> Height (hours)
<br /> ft m ft m
<br /> Class I 25 7,6 30 9,1 Wet 6 30 psi 14 ft x 14 ft 250 gpm 1
<br /> through Class (2,1 bar) (4,3 m x 4,3 m) (950 L/min)
<br /> Palletized, IV,
<br /> Solid-Piled, encapsulated 30 9,1 35 11 Wet 8 40 psi 12 ft x 12 ft 250 gpm 1
<br /> Bin Box, and (2,8 bar) (3,7 m x 3,7 m) (950 L/min)
<br /> Shelf,or unencapsu-
<br /> Back-to-Back lated,
<br /> Shelf Storage and cartoned 30 9,1 35 11 Wet 8 40 psi 14 ft x 14 ft 500 gpm 1.5
<br /> non-expanded (2,8 bar) (4,3 m x 4,3 m) (1900 L/min)
<br /> plastics
<br /> TABLE A
<br /> NFPA 13, CHAPTER 21 -ALTERNATIVE SYSTEM DESIGN
<br /> PALLETIZED, SOLID-PILED, BIN BOX, SHELF, OR BACK-TO-BACK SHELF STORAGE
<br /> OF CLASS I-IV AND CARTONED NON-EXPANDED PLASTIC COMMODITIES
<br /> Storage Commodity Max. Max. Type of Number Min. Max. Hose Water
<br /> Arrangement Class Storage Ceiling/ System of Design Operating Coverage Stream Supply
<br /> Height Roof Sprinklers Pressure Area Allowance Duration
<br /> Height (hours)
<br /> ft m ft m
<br /> Class I 25 7,6 30 9,1 Wet 6 30 psi 14 ft x 14 ft 250 gpm 1
<br /> through Class (2,1 bar) (4,3 m x 4,3 m) (950 L/min)
<br /> Sprinkler IV,
<br /> protection encapsulated 30 9,1 35 11 Wet 8 40 psi 12 ft x 12 ft 250 gpm 1
<br /> and
<br /> criteria for unencapsu (2,8 bar) (3,7 m x 3,7 m) (950 L/min)
<br /> •
<br /> open frame lated,
<br /> rack storage and cartoned 30 9,1 35 11 Wet 8 40 psi 14 ft x 14 ft 500 gpm 1.5
<br /> non-expanded (2,8 bar) (4,3 m x 4,3 m) (1900 L/min)
<br /> plastics
<br /> TABLE B
<br /> NFPA 13, CHAPTER 21 -ALTERNATIVE SYSTEM DESIGN
<br /> OPEN-FRAME RACK(SINGLE, DOUBLE,AND MULTIPLE ROW)STORAGE
<br /> OF CLASS I-IV AND CARTONED NON-EXPANDED PLASTIC COMMODITIES
<br /> Care and as well as with the applicable stan- Sprinkler Assemblies with 1 Inch
<br /> dards of any authorities having juris- NPT Pipe Threads
<br /> Maintenance diction.Contact the installing contrac- Specify: Model EC-25 Extended Cov-
<br /> tor or product manufacturer with any erage Upright Sprinkler (TY9128),
<br /> The TYCO Model EC-25 Upright questions. (specify) temperature rating, natural
<br /> Sprinkler must be maintained and ser- Automatic sprinkler systems are rec brass, and P/N (specify):
<br /> viced in accordance with this section. ommended to be inspected, tested, 165°F(74°C) P/N 58-450-1-165
<br /> Before closing a fire protection sys- and maintained by a qualified Inspec- 214°F(101°C) P/N 58-450-1-214
<br /> tern main control valve for mainte- tion Service in accordance with local "Special Order"Sprinkler
<br /> nance work on the fire protection sys- requirements and/or national codes. Assemblies with ISO 7-R1 Pipe
<br /> tem that it controls, obtain permission Threads
<br /> to shut down the affected fire protec- LimitedSpecify: Model EC-25 Extended Cov-
<br /> tion system from the proper authori- erage Upright Sprinkler (TY9128) with
<br /> ties and notify all personnel who may warranty ISO 7-R1 pipe thread, (specify) tern-
<br /> be affected by this decision. perature rating, natural brass, and P/N
<br /> Inspection, testing, and maintenance For warranty terms and conditions, (specify):
<br /> must be performed as indicated be- visit www.tyco-fire.com. 165°F(74°C) P/N 58-451-1-165
<br /> low and in accordance with the local 214°F(101°C) P/N 58-451-1-214
<br /> requirements and/or national codes. Ordering Sprinkler Wrench
<br /> Any impairment must be immediately Specify W-Type 1 Sprinkler Wrench,
<br /> corrected. Procedure P/N 56-872-1-025
<br /> The owner is responsible for the in- Contact your local distributor for avail-
<br /> spection, testing, and maintenance of ability. When placing an order, indi-
<br /> their fire protection system and devic- cate the full product description and
<br /> es in compliance with this document, Part Number(P/N).