Laserfiche WebLink
TFP213 <br /> Page 4 of 4 <br /> Storage Commodity Max. Max. Type pe of Number Min. Max. Hose Water <br /> Arrangement Class Storage Ceiling/ System of Design Operating Coverage Stream Supply <br /> Height Roof Sprinklers Pressure Area Allowance Duration <br /> Height (hours) <br /> ft m ft m <br /> Class I 25 7,6 30 9,1 Wet 6 30 psi 14 ft x 14 ft 250 gpm 1 <br /> through Class (2,1 bar) (4,3 m x 4,3 m) (950 L/min) <br /> Palletized, IV, <br /> Solid-Piled, encapsulated 30 9,1 35 11 Wet 8 40 psi 12 ft x 12 ft 250 gpm 1 <br /> Bin Box, and (2,8 bar) (3,7 m x 3,7 m) (950 L/min) <br /> Shelf,or unencapsu- <br /> Back-to-Back lated, <br /> Shelf Storage and cartoned 30 9,1 35 11 Wet 8 40 psi 14 ft x 14 ft 500 gpm 1.5 <br /> non-expanded (2,8 bar) (4,3 m x 4,3 m) (1900 L/min) <br /> plastics <br /> TABLE A <br /> NFPA 13, CHAPTER 21 -ALTERNATIVE SYSTEM DESIGN <br /> PALLETIZED, SOLID-PILED, BIN BOX, SHELF, OR BACK-TO-BACK SHELF STORAGE <br /> OF CLASS I-IV AND CARTONED NON-EXPANDED PLASTIC COMMODITIES <br /> Storage Commodity Max. Max. Type of Number Min. Max. Hose Water <br /> Arrangement Class Storage Ceiling/ System of Design Operating Coverage Stream Supply <br /> Height Roof Sprinklers Pressure Area Allowance Duration <br /> Height (hours) <br /> ft m ft m <br /> Class I 25 7,6 30 9,1 Wet 6 30 psi 14 ft x 14 ft 250 gpm 1 <br /> through Class (2,1 bar) (4,3 m x 4,3 m) (950 L/min) <br /> Sprinkler IV, <br /> protection encapsulated 30 9,1 35 11 Wet 8 40 psi 12 ft x 12 ft 250 gpm 1 <br /> and <br /> criteria for unencapsu (2,8 bar) (3,7 m x 3,7 m) (950 L/min) <br /> • <br /> open frame lated, <br /> rack storage and cartoned 30 9,1 35 11 Wet 8 40 psi 14 ft x 14 ft 500 gpm 1.5 <br /> non-expanded (2,8 bar) (4,3 m x 4,3 m) (1900 L/min) <br /> plastics <br /> TABLE B <br /> NFPA 13, CHAPTER 21 -ALTERNATIVE SYSTEM DESIGN <br /> OPEN-FRAME RACK(SINGLE, DOUBLE,AND MULTIPLE ROW)STORAGE <br /> OF CLASS I-IV AND CARTONED NON-EXPANDED PLASTIC COMMODITIES <br /> Care and as well as with the applicable stan- Sprinkler Assemblies with 1 Inch <br /> dards of any authorities having juris- NPT Pipe Threads <br /> Maintenance diction.Contact the installing contrac- Specify: Model EC-25 Extended Cov- <br /> tor or product manufacturer with any erage Upright Sprinkler (TY9128), <br /> The TYCO Model EC-25 Upright questions. (specify) temperature rating, natural <br /> Sprinkler must be maintained and ser- Automatic sprinkler systems are rec brass, and P/N (specify): <br /> viced in accordance with this section. ommended to be inspected, tested, 165°F(74°C) P/N 58-450-1-165 <br /> Before closing a fire protection sys- and maintained by a qualified Inspec- 214°F(101°C) P/N 58-450-1-214 <br /> tern main control valve for mainte- tion Service in accordance with local "Special Order"Sprinkler <br /> nance work on the fire protection sys- requirements and/or national codes. Assemblies with ISO 7-R1 Pipe <br /> tem that it controls, obtain permission Threads <br /> to shut down the affected fire protec- LimitedSpecify: Model EC-25 Extended Cov- <br /> tion system from the proper authori- erage Upright Sprinkler (TY9128) with <br /> ties and notify all personnel who may warranty ISO 7-R1 pipe thread, (specify) tern- <br /> be affected by this decision. perature rating, natural brass, and P/N <br /> Inspection, testing, and maintenance For warranty terms and conditions, (specify): <br /> must be performed as indicated be- visit www.tyco-fire.com. 165°F(74°C) P/N 58-451-1-165 <br /> low and in accordance with the local 214°F(101°C) P/N 58-451-1-214 <br /> requirements and/or national codes. Ordering Sprinkler Wrench <br /> Any impairment must be immediately Specify W-Type 1 Sprinkler Wrench, <br /> corrected. Procedure P/N 56-872-1-025 <br /> The owner is responsible for the in- Contact your local distributor for avail- <br /> spection, testing, and maintenance of ability. When placing an order, indi- <br /> their fire protection system and devic- cate the full product description and <br /> es in compliance with this document, Part Number(P/N). <br /> GLOBAL HEADQUARTERS 11400 Pennbrook Parkway,Lansdale,PA 19446 I Telephone+1-215-362-0700 <br /> Copyright©2014 Tyco Fire Products,LP. All rights reserved. Vico <br /> TEFLON is trademark of The DuPont Corporation. " Fire Protection Products <br />