Rhvac-Residential&Light Commercial HVAC Loads Elite Software Development,Inc.
<br /> Auer Steel(New Hope) Midwest Custom Const.
<br /> Plymouth,MN 5.5441 E Page 7
<br /> System 11 Zone 1 Summary Loads (Average Load Procedure for Rooms
<br /> Component Area Sen Lat Sen Total
<br /> Description Ouan Loss Gain Gain Gain,
<br /> 2A-v-o: Glazing-Double pane low-e(e=0.60),operable 239.8 12,132 0 14,417 14,417
<br /> window,vinyl frame, u-value 0.55, SHGC 0.61
<br /> 11 P: Door-Metal - Polyurethane Core 21 560 0 207 207
<br /> 12E-Osw:Wall-Frame, R-19 insulation in 2 x 6 stud 2007.2 12,556 0 3,467 3,467
<br /> cavity, no board insulation, siding finish, wood studs
<br /> 12E-Osw: Part-Frame, R-19 insulation in 2 x 6 stud cavity, 301.5 1,435 0 205 205
<br /> no board insulation, siding finish,wood studs
<br /> 1613-30: Roof/Ceiling-Under Attic with Insulation on Attic 108 318 0 200 200
<br /> Floor(also use for Knee Walls and Partition
<br /> Ceilings), Vented Attic, No Radiant Barrier, Dark
<br /> Asphalt Shingles or Dark Metal,Tar and Gravel or
<br /> Membrane, R-30 insulation
<br /> 16A-38: Roof/Ceiling-Under Attic with Insulation on Attic 1232 2,947 0 2,498 2,498
<br /> Floor(also use for Knee Walls and Partition
<br /> Ceilings), Unvented Attic, No Radiant Barrier, Any
<br /> Roofing Material,Any Roof Color, R-38 insulation
<br /> 19B-s8.25p: Floor-Over enclosed unconditioned crawl 1064 1,756 0 439 439
<br /> space, R-4 insulation on exposed walls, sealed crawl
<br /> space, passive, 8.25 inch R-29.77 SIP panels with R-
<br /> 3.85 per inch EPS core
<br /> 20P-30: Floor-Over open crawl space or garage, Passive, 288 927 0 181 181
<br /> R-30 blanket insulation, any cover
<br /> Subtotals for structure: 32,631 0 21,614 21,614
<br /> People: 0 0 0 0
<br /> Equipment: 0 0 0
<br /> Lighting: 0 0 0
<br /> Ductwork: 0 0 0 0
<br /> Infiltration: Winter CFM: 104, Summer CFM: 52 10,176 1,036 1,272 2,308
<br /> System 1, Zone 1 Load Totals: 42,807 1,036 23,297 24,333
<br /> Check FIures - ----- - ----- - --- ----
<br /> Supply CFM: 1,091 CFM Per Square ft.: 0.475
<br /> Square ft. of Room Area: 2,296 Square ft. Per Ton: 1,132
<br /> Volume(W)of Cond. Space: 19,432
<br /> Zone Loads -- -- - -- - -—_ ---- --- - _ _ --- -- -- - ---- �
<br /> Total Heating Required: 42,807 Btuh 42.807 MBH
<br /> Total Sensible Gain: 23,297 Btuh 96 %
<br /> Total Latent Gain: 1,036 Btuh 4 %
<br /> Total Cooling Required: 24,333 Btuh 2.03 Tons(Based On Sensible+Latent)
<br /> Notes
<br /> Rhvac is an ACCA approved Manual J and Manual D computer program.
<br /> Calculations are performed per ACCA Manual J 8th Edition, Version 2,and ACCA Manual D.
<br /> All computed results are estimates as building use and weather may vary.
<br /> Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
<br /> your design conditions.
<br /> C:\...\Midwest Custom Const-Countryside Solutions.rhv Thursday, November 20, 2014, 9:36 AM