Laserfiche WebLink
11. Complete job shall be guaranteed for a pe�riod of one year after date of job acceptance by owner.Any <br /> work,material or equipment found to be Eaulty during that period shall be corrected at once upon <br /> written notification,at the expense of the ;5ub-contractor. <br /> 12. All conduit only(C.O.)shall have a pull v��ire or rope. <br /> 13. All work shall be per installation drawing:;and details.Provide Contractor with one set of complete <br /> electrical"as installed"mazkups at the completion of the job showing actual dimensions,routings <br /> and circuits. <br /> 14. All brochures,operating manuals, catalogs, shop drawings, etc.,shall be tumed over to the <br /> Contractor at job completion. <br /> 15. Use t-tap connections on all multi-circuits with common neutral conductor for lighting fixtures. <br /> 16. All conductors shall be copper. <br /> 17. All circuit breakers,fuses and electrical equipment shall have a minimum interrupting short circuit <br /> rating of 10,000 A.I.C. Sub-contractor shall verify the Site requirements. <br /> 18. The entire electrical installation shall be gr.ounded as required by all applicable codes and NEC. <br /> 19. Patch,repair,and paint any area that has been damaged in the course of the electrical work. <br /> 20. Penetrations in fire rated walls shall be sea�led in accordance with applicable codes. <br /> 21. Power wire and cable conductors shall be��opper#12 AWG minimum unless specifically noted <br /> otherwise on drawings. <br /> 22. Grounding conductors shall be tinned cop��er,annealed, and solid or stranded and sized as shown on <br /> drawings. . . <br /> 23. Meter socket amperes,voltage,number of phases shall be as noted on the drawings,Manufactured <br /> by"Square D Company"or approved equa�l. <br /> 24. All materials shall be UL listed. <br /> 25. Conduit <br /> Rigid conduit shall be IJL labeled galvaniz;ed zinc coated with zinc interior and shall be used when <br /> installed in or under concrete slabs in cont3ct with the earth,under public roadways, in masonry <br /> walls or exposed on building exterior.Rigid conduit in contact with earth shall be %2 lap wrapped <br /> with Hunts wrap process No.3.Flexible metallic conduit shall have IJL listed label and may be used <br /> where permitted by code.Fittings shall be `jake"or"squeeze"type;seal tight flexible conduit.All <br /> conduit shall have full size equipment ground wire. Conduit runs shall be surface mounted in ceilings <br /> or walls unless indicated otherwise. Conduit indicated shall run parallel or at right angles to the <br /> ceiling,floor,or beams.Verify e�cact rout'vig of all exposed conduit with the Owner prior to <br /> installing.No horizontal conduits shall be lbelow 7'-6"Above Finish Floor(A.F.F).No BX or <br /> ROMEX cable is permitted.All underground conduit shall be PVC schedule 40(unless noted <br /> otherwisel at a minimum depth of 30"below grade or 6"below frost line. <br /> 26. All electrical equipment shall be labeled with permanent engraved plastic labels. <br /> 27. Coordinate the electrical service with the local utility company. <br /> CNS/US WEST COMMUNICATIONS ELECTRICAL MATERIALS AND METHODS <br /> SMMA NO.96419.16 16000-2 17 DEC.96 <br />