Laserfiche WebLink
35,100.9. ELECTRICAL_ CONTROL: The contractor shall furnish and install a <br />completely automatic duplex control system including fused main switch, trans- <br />fer switch, auxiliary power receptacle, motor starting and protection equip- <br />ment and a pump control system. The control pane', %hall he furnished by one <br />control manufacturer. <br />39,100.9.1. Control: The pump control shall operate the two pumps based on <br />the liquid level in the wet well. fin a rising 'evel the lead pump shall be <br />started followed by the lag pump can a continuing rising level operating <br />pumps shall he stopped at a common low level. Pumps shal' automatically <br />alternate lead duty every cycle. Three float switches shall he provided for <br />pump control and a fourth switch for a high water alarm condition. <br />'15,100.9.2. Panel: The panel shall enclose all electrical and service equip- <br />ment including the disconnect and transfer switches, power company's meter and <br />metering equipment, motor control and supervis!)ry control equipment. The me- <br />tering equipment shall he in a separate section of the panel that is sealable <br />by the power companv. A lexan window, approximately 6" x 6", shall he placed <br />in the door to allow reading of the meter with panel doors closed. <br />ON <br />The panel enclosure shall he low profile, weatnerproof, tamperproof, rain - <br />tight constructed in accordance with NEM,A 3T standards. The enclosure shall <br />tie constructed of not less than 14 gauge cold rolled steel. The enclosure <br />shall be phosphatized before app.tcation of a rust-int-ibiting prime coat. The <br />�! finish coat shall be exterior grade baked enamel green color to match the <br />power companv's transformer. <br />1� <br />The panel shall be equipped with two or more dead front, gasketed doors with a <br />three-point latching system with single, padlockable hand].- for PA^_11 door. <br />Tumbler type door locks are not acceptable. Ning,.-a ghall he piano type. <br />The panel shall be free standing enclosure and shall be: low profile with a <br />maximum 46 inches in height. Provide 4kirts to cover open area under panel <br />14 where floor stands are used. 'Where nec-essary to accommodate equipment and <br />64 devices, several sections shall he bolted together to form a single structure. <br />Mounting and location of the control panel shall he subject to the approval of <br />P4 the Engineer. <br />The enclosure shall be furnished with internal, piano hinged c',00rs. Motor <br />controls, circuit breakers, resets, indicating lights, timers, .-tc. shall be <br />mounted to be accessible with interior doors closed. All devices �•n interior <br />doorr. shall he labeled with engraved, laminated plastic nameplates, interior <br />devices, relays, timers, terminals. Nt, . .41,All he marked with plastic tape or <br />tags. <br />the control panel components shall `u !I] labeled and manufactured in the <br />United States. It is the intention 0 this rpgniroment that the panel 1+e <br />constructed to 111. standards without reyuir�nk th-- manufacturer to -, a "I <br />approved manufacturing faciliry or rer1.:iriry !hc Pntir,- panel rn havw a Ill. <br />4pai. <br />3 5 , 100-1 <br />n-5A41c <br />rt,pvright 1Q85 <br />Ronestroo, Rusenp, Anderlik <br />b Associates, Inc. <br />