J <br /> SFMD Fact Sheet INS-FACT 1999-11 <br /> November 1, 1999 <br /> / Page 2 of 4 <br /> posts not less than 3 feet above the ground, and(5) located not less than 5 feet from the <br /> tank. <br /> 7. Dispensers shall be protected against physical damage from vehicles by mounting on a concrete <br /> island 6 inches or more in height or by other approved means. <br /> S. There shall be an emergency shut-off device located between 20 feet and 100 feet from the dispense: <br /> Activation of the emergency shut-off shall shut down transfer of fuel to the dispenser and shall close <br /> all valves that supply fuel to the dispenser. The emergency shut-off shall be distinctly labeled <br /> EMERGENCY FUEL SHUTDOWN DEVICE. <br /> 9. Within 75 feet of the dispenser,there shall be a portable fire extinguisher rated at a minimum 2-A, <br /> 20-B:C. The fire extinguisher shall be inspected annually by qualified personnel. <br /> 10. Signs prohibiting smoking, dispensing into unapproved containers, and requiring vehicle engines to <br /> be stopped during fueling shall be conspicuously posted within sight of each dispenser. W1�ea open u. <br /> the public or when there are empiovees that are under 16 years old. there shall be a sia*1 stating d. e <br /> minimum ase to dispense :lammabieicombustibie liquids is 16. <br /> 1. Weeds. grass. brush. rmash and other combustible materials shall'_cept at least 10 feet from anAST. <br /> _. ASTs snail have a minirlum 3-:pet separation berween ta_nkcs. Larger t ^.!cs may=eauire:r_ore space. <br /> .�. <br /> Storage vessels for LP-gas an4 CSG stall be iocated=0 feet or more from.SST's. Suitabie-means <br /> shall be provided w prevent the accumulation of liquids under adjacent I- gas containers such as b}' <br /> dLkeS -Jlversion curbs or_JradinQ When HJT s arm: within a dL�ed area. :ham _?-?'.S containers 3;.a:1 <br /> outside the diked area and at least 10 feet away Tom the centerline of the :nail or the diked area. <br /> 1-. ASTs shall nave warning si—ps or labels to identif�i the tank contents _o axer^ency personnel. <br /> i:. :SSTs require nor-.:mai and emer2encv ents. The normal vent shall to minate at least 12 feet above th <br /> Q*ound level and 5 feet from buildins Ot7e.^1n2S OrproDert.v lures that Can aL'llt'1Don. <br /> 16. Elec.;cai eauit rrmeat shall be installed in accordance with the liinnesota State =lecarical Code. <br /> 17. Dispersing is required to be under the supervision of a qualified attendant at all times. The attendantz <br /> primary function shall be to supe^rise, observe and control the dispensing of motor fuels. The <br /> attendant shall prevent the dispensing of flammable and combustible liquids and flammable gases <br /> into containers not in compliance with the Minnesota Uniform Fire Code. The attendant shall also <br /> control sources of ignition, give immediate attention to accidental spills or releases, and be prepared <br /> to use fire extinguishers. A method of communicating with the fire department shall be provided for <br /> the attendant. <br /> 13. Contact the State Fire Marshal Division for requirements that may apply to situations such as: <br /> • Dispensing at a bulk plant,marina or resort • Dispensing of LPG, CNG, etc. <br /> • Dispensing inside a building • Dispensing from tank vehicles <br /> 0 Dispensing into containers • Unsupervised dispensing <br /> 19. Pages 3 and 4 of this information sheet contain additional requirements specific to the type of above <br /> ground tank installation used for dispensing. <br />