Laserfiche WebLink
• � <br /> . . '� <br /> :. <br /> 23 = 9 ft + 5 ft + 9 ft <br /> ; <br /> A Pump must b� Selected to Deliver at least ;, <br /> 39.96 Gallons per Minute 'f� <br /> 23 Feet of Total Head <br /> 1. Tank Shape: UNKOWN SHAPE <br /> 2. Bottom Area of Septic Tank: 32 ft <br /> Gallons per Inch: 20 <br /> 3... Gallons over Pump: 12 <br /> 12 = 20 x t 10 + 2j <br /> 4. Calculate Total Pumbout Volume <br /> � Calculate Dose <br /> To maximize pump life Daily Flow is will Divide by 4 <br /> 600 / 4 = 150 gallons <br /> Calculate Drainback <br /> Total pi�e Length: 230 feet <br /> Liquid Volume of Pipe: 17.43 gallons per 100 feet <br /> Drainback (gal) = Length (ft} x Volume (gal/100ft) <br /> 0 gal = 230 ft x 17.43 gdl/100ft <br /> Total Pumpout = Dose + Drainback <br /> 150 gal = 150 gal + 0 gal <br /> 5. Volume for Alarm using 3 inch Depth <br /> 60 gal = 3 inches x 20 gal <br /> 6. Recommended Calculate Reserve Capacity (75$ of Daily Flow) <br /> 450 aal = ..?5 x 600 gal <br /> 7. Calculated Total Gallons <br /> 672 gal = 12 + 150 + 60 + 450 <br /> 8. Total Depth {Total gallon dividAd by gallon per inch} <br /> 34 .09 inches = 672 / 20 <br /> 9. Flcat Separation Distance = Total Fumpout Volume / Gallon per inch <br /> 8 = 150 gal / 20 qal <br /> 1. Tank Shape: UNKOWN SHAPE <br /> 2. Bottom Area of Septic Tank: 32 ft <br /> Gallons per Inch: 20 <br /> 3. Gallons over Pump: 12 <br /> 12 = 20 x ( 10 + 2) <br /> 4. Calculate Total Pumpout Volume <br /> Calculate Dose <br /> To maximize pump iife uaiiy riow is wiii Divide py 4 <br />