. � <br /> -I.B.C. table 2902.1 requires one drinking fountain <br /> -Drinking fountain must be in compliance with state code section 1341.0446 <br /> -I.B.C. 1209 Requires toilet room floors to be a smooth, hard, nonabsorbent surface that <br /> extends up the wall a min. of 6" <br /> -I.B.C. 1209.2 Requires walls within 2 feet of urinals and water closets to be a smooth, <br /> hard, nonabsorbent surface to a height of 4 feet above the floor <br /> -State code section 1341.0422, subpart 2 item A Requires the accessible route to coincide <br /> with the route for the general public. Proposed ramp location unacceptable <br /> -Door hardware must be in compliance with section 1341.0442 subp. 9 <br /> -State code section 1341.0520 Requires counters to be accessible in compliance with <br /> sectionl 341.0480 <br /> -Plumbing plans are required to be received by the state plbe code division <br /> -Kitchen plans are required to be received by Hennepin county health dept. <br /> -Plans are required to be submitted to the Met Council for SAC determination <br /> �� �� � � z <br />