Laserfiche WebLink
10/W2017 04:37 FAX lib 006 <br /> Table 1: Minimum Insulation Thidkaesafor CFrcu/ating Hot Water Pipes. <br /> Insulation Thickness in Indies by Pipe Sizes <br /> Heated Water Non-Circulating Runouts Circulating Mains and Runouts <br /> Temperature(FZ Up to 1" Up to 1.25" 1.5"to 2.0" Over 2" <br /> 170-180 0.5 1.0 1.5 2.0 <br /> 140-160 0.5 0.5 1.0 1.5 <br /> 100-130 0.5 0.5 0.5 1.0 <br /> Table 2: minimums Insulation Thickness for HVAC Pipes. <br /> Fluid Temp. Insulation Thickness in Inches by Pipe Sizes <br /> Piping System Types Range(F) 2"Runouts 1"and Less 1.25"to 2" 2.5"t0 4" <br /> Heating Systems <br /> Low Pressurelrenperature 201-250 1.0 1.5 1.5 2.0 <br /> Low Temperature 120-200 0.5 1.0 1.0 1.5 <br /> Steam Condensate(for feed water) Any 1.0 1.0 1.5 2.0 <br /> Cooling Systems <br /> Chilled Water,Refrigerant 40-55 0.5 0.5 0.75 1.0 <br /> and Brine Below 40 1.0 1.0 1.5 1.5 <br /> NOTES TO FIELD (Building Department Use Only) <br />