Laserfiche WebLink
• <br /> II.Plum. ng Fixture Requirements <br /> I have rev -wed the plumbing fixture requirements for a total building occupancy of 2066 with <br /> the owner At this occupancy, the fixture count is 4 water closets short for women as indicated in <br /> the Dece .er 2 memo. The owner ha, indicated that the building will never have that many <br /> occupants I or any of its potential community functions; therefore, they are concerned that the <br /> total fixtu i- count is overdesigraed to a significant degree. <br /> I have 'alculated the maximum allowable occupant load based on the fixtures shown in the <br /> plan as fol ows (based on LTBC Table A-29-A): <br /> 6 fixtures u r men (located in men's toilet room) =725 occupants <br /> 11 fixture: for women (6 fixtures in women's toilet room, 1 in referees' room, 4 in team rooms) <br /> =700 occ pants <br /> Total allo able occupant load based on available fixtures = 1425 occupants <br /> The owne suggests that the building occupancy could be limited to 1425 occ. already provided <br /> for by the tures as designed. They are willing to enter into an agreement with the city to not <br /> exceed thi• occupancy. Limiting the occupancy to 1425 also eases the exit scheme although the <br /> building pl,n will continue to reflect exiting for an occupant load of 2066. <br /> Lyle, pl ase call we with any questions and/or comments. <br /> Sincerel <br /> rr/ !' ii/f F/I/r <br /> Victor Pec .ty AIA <br /> Ted Rozeb om Architects <br /> E60 EJ NOOEI3Z011 alL 08L5 ILfi ZI9 7CV,3 gI :ZI 96/6T/ZI <br />