Laserfiche WebLink
2oa s -Ob 9 <br /> • <br /> bleuWorldwide ,AN)� <br /> Fire Protection <br /> Contacts www.tyco-fire.com <br /> Products <br /> Model CV-1F Grooved End <br /> Swing Check Valves <br /> 2 to 12 Inch (DN50 to DN300) <br /> General Never remove any piping component <br /> nor correct or modify any piping defi- <br /> Descri tion ciencies without first de-pressurizing ! <br /> I" and draining the system. Failure to do <br /> The TYCO Model CV-1 F Grooved End so may result in serious personal injury, <br /> Swing Check Valve is a compact and property damage, and/or impaired <br /> rugged swing-type unit that allows device performance. <br /> water flow in one direction and prevents The owner is responsible for maintain- f <br /> flow in the opposite direction.A resilient ing their fire protection system and <br /> elastomer seal facing on the spring- devices in proper operating condition. <br /> loaded clapper ensures a leak-tight seal The installing contractor or manufac- <br /> and non-sticking operation.The Model turer should be contacted with any <br /> CV-1F Check Valves are designed to questions. <br /> minimize hammer caused by flow <br /> reversal. Technical Installation <br /> The Model CV-1F Grooved End Swing <br /> Check Valve is furnished with grooved Data The Model CV-1F Grooved End Swing <br /> ends and can be installed using Grinnell Check Valves are to be installed in <br /> Grooved Couplings or GRINNELL Approvals accordance with this section: <br /> Figure 71 Flange Adapters. The UL, C-UL, and FM <br /> Model CV-1F Check Valves have been Step 1. The arrow cast on the Body <br /> designed with a removable cover for Sizes must point in the direction of the flow. <br /> ease of field maintenance.These valves 2 to 12 Inch (DN50 to DN300) Step 2. Valves installed vertically <br /> can be installed horizontally(with cover must be positioned with the flow in the <br /> in the upward position)or vertically with Maximum Working Pressure upward direction. <br /> the flow in the upward direction. Refer 300 psi(20,7 bar) <br /> Figure 4. Step 3. Valves installed horizontal- <br /> toValve Assembly Finish ly must be positioned with the Cover <br /> A Maintenance Check Valve Kit Red, non-lead paint facing up. Refer to Figure 4. <br /> (TFP1555) is available to allow the Step 4. Grooved end pipe couplings <br /> maintenance procedure of back- used with the Model CV-1F Grooved <br /> flushing through the fire department <br /> connection without removing the Model End Swing Check Valve must be <br /> installed in accordance with <br /> CV-1F Grooved End Swing Check Valve manufac <br /> from the pipe line. turer's instructions. <br /> The Model CV-1F Grooved End Swing NOTE: Valves installed too close to <br /> Check Valves are a redesign for the sources of unstable flow will shorten <br /> Central Figure 590E and GRINNELL <br /> he the life of the valve and may potentially <br /> Figure 590F. damage the system. Valves should be <br /> installed a reasonable distance down- <br /> stream from pumps, elbows, expand- <br /> NOTICEers, reducers, or other similar devices <br /> The TYCO Model CV-1F Grooved End to extend the valve life. Standard piping <br /> Swing Check Valves described herein practices call for a minimum of five(5) <br /> must be installed and maintained in times the pipe diameter for general use. <br /> compliance with this document and <br /> with the applicable standards of the <br /> National Fire Protection Association,in <br /> addition to the standards of any authori- <br /> ties having jurisdiction. Failure to do so <br /> may impair the performance of this <br /> device. <br /> Page 1 of 4 APRIL 2014 TFP1550 <br />