Laserfiche WebLink
' AutoPeaking Summary <br /> ESCAPE FIRE Page 13 <br /> JEM TECHNICAL Date 3/31/15 <br /> Auto Peaking Summary- List of Pipes for Area Calculated ' <br /> � , <br /> Left Right <br /> Side Side <br /> From To Length From To Length <br /> 101 1 43.833 6 201 33.833 <br /> 102 7 43.833 12 202 33.833 <br /> 103 13 73.833 15 203 33.833 <br /> 101 1 43.833 6 201 33.833 <br /> 102 7 43.833 12 202 33.833 <br /> 103 13 73.833 15 203 33.833 <br /> Flow Safety Pressure <br /> Required Margin Differential <br /> Left 10.000 I 1559.914 11.337 -0.018 <br /> Area Calculated I 1560.497 11.319 0.000 <br /> Right 10.000 I 1560.823 11.429 -0.110 <br /> Typical Distance Between Heads = 10.000 <br /> Split Point Used in Worst Area Peaked = 3A <br /> Split Point Used in Area Calculated = 3A <br /> Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 <br />