Laserfiche WebLink
Final Calculations - Hazen-Williams <br /> ESCAPE FIRE Page 12 <br /> JEM TECHNICAL Date 3/31/15 <br /> Hyd. Qa Dia. Fitting Pipe Pt Pt 4 <br /> Ref. "C" or Ftng's Pe Pv ******* Notes ****** `'.. <br /> Point Qt Pf/Ft Eqv. Ln. Total Pf Pn <br /> -------------- <br /> M <br /> \M 1060.50 6.357 11 12.573 6.000 28.462 <br /> to 120.0 0.0 12.573 0.0 <br /> TOR 1060.5 0.0312 0.0 18.573 0.580 Vel = 10.72 <br /> TOR 0.0 6.357 0.0 20.000 29.042 <br /> to 120.0 0.0 0.0 8.662 <br /> BOR 1060.5 0.0312 0.0 20.000 0.623 Vel = 10.72 <br /> BOR 0.0 6.357 2G 7.544 2.000 38.327 <br /> to 120.0 0.0 7.544 3.366 * Fixed loss = 2.5 <br /> FLG 1060.5 0.0312 0.0 9.544 0.298 Vel = 10.72 <br /> FLG 0.0 8.27 1E 28.468 590.000 41.991 <br /> to 140.0 2F 28.468 124.942 0.433 <br /> TEST 1060.5 0.0065 2G 12.652 714.942 4.656 Vel = 6.33 <br /> 1T 55.354 <br /> 500.00 Qa = 500.00 <br /> 1560.50 47.080 K Factor= 227.43 <br /> Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 <br />