Laserfiche WebLink
B. Install sprinklers centered or at'%points on ceiling tiles in lay-in acoustic ceilings. , <br /> C. Sprinklers shall not be installed directly over pool surface. <br /> 3.07 FIELD QUALITY CONTROL , <br /> A. Flush, test, and inspect sprinkler piping systems in accordance with NFPA 13. Provide written witnessed <br /> documentation with four(4)copies sent to the engineer. ' <br /> B. Replace piping system components which do not pass the test procedures specified, and re-test repaired portion of <br /> the system. , <br /> 3.08 SYSTEM IDENTIFICATION <br /> A. Furnish and install permanent,plastic laminated,engraved signs identifying each sprinkler zone,the area it controls, ' <br /> and the hydraulic design data. <br /> B. Furnish and install permanent, plastic laminated, engraved signs identifying the inspectors test connection and , <br /> which zone they service. <br /> END OF SECTION 15300 , <br /> 15300-8 No.99132-CP2 ' <br />