H. Equipment piping shall also include wastes and drains which are safewasted without a direct connection. This shall <br /> include drains from drain pans,plenum drains,backflow preventers and automatic air vents,etc. <br /> I. Service piping to fixtures and equipment shall be installed concealed wherever possible. Conceal piping within the <br /> wall adjacent to the equipment or in the enclosures provided by the equipment supplier, as indicated on the <br /> drawings. For size of enclosures and exact locations,see equipment shop drawings. <br /> J. Exposed piping shall be installed in a sanitary manner for ease in cleaning. <br /> 3.06 CONNECTIONS TO MISCELLANEOUS EQUIPMENT <br /> A Due to the fact that the manufacturer of the equipment purchased may vary slightly from that specified and, <br /> therefore, requires some rearranging of equipment different from that indicated on the drawings, the Contractor <br /> shall make connections to such rearranged equipment without additional cost to the Owner. That is for initial <br /> installation arrangement other than that indicated on the drawings. <br /> i <br /> B. This Contractor shall make all water,waste,vent, steam,condensate retum,water heating and cooling, condensate <br /> drain pan piping, ductwork connections, etc., to all equipment in this building whether or not such equipment is <br /> furnished by this Contractor, other Contractors or by the Owner. This includes furnishing and installing piping, <br /> shut-off valves, unions, fittings, ductwork, air control devices and insulation. Also included in this work are <br /> connections, including shut-off valves,backflow preventers,pressure reducing valves,unions, double check valve <br /> assembly,open wastes and traps to make up supply water to building environmental system equipment. <br /> C. The Mechanical Contractor shall coordinate work between the various trades to ensure proper installation and <br /> operation of all systems. Do not install ductwork so as to cover electrical junction boxes unless this contractor <br /> provides approved access panels in both layers of duct. <br /> 3.07 FOUNDATIONS AND SUPPORTS <br /> A. Foundations, supports, anchors, concrete bases, anchor bolts, sleeves, grouts, shims, etc., required for properly <br /> placing mechanical equipment fiurnished under this contract shall be provided by this Contractor,unless specifically <br /> stated otherwise. Housekeeping pads, four(4) inches thick, of 140 pcf dense concrete, shall be furnished for all <br /> mechanical equipment located on floor slabs. See architectural and structural drawings for concrete work to be <br /> famished by General Contractor. Coordinate exact locations of concrete pads with General Contractor. <br /> 3.08 TESTS <br /> A. General. Tests shall be performed on all systems. Tests shall be repeated until each system is proven acceptable. <br /> 1. All work shall be inspected,tested and approved as required by the State of Minnesota and local regulations. <br /> Tests shall be made in the presence of proper inspectors and the Architect/Engineer or their duly authorized <br /> representatives. All tests shall be made by the Contractor at his own expense, and he shall furnish three(3) <br /> test certificates to the Architect/Engineer for approval. <br /> 2. All work shall prove absolutely tight under required tests. All tests of piping systems, except final tests of <br /> completed systems shall be made before pipe is covered or connected to fixtures and equipment. <br /> 3. All gauges,tools,pumps,air compressor or other equipment required for testing and initial adjusting of piping <br /> systems shall be purchased and provided by this Contractor. <br /> 4. See respective Division 15 sections for tests required under that specific section of the specification. <br /> B. Ventilation and Air Conditioning Systems. <br /> 1. All ventilating systems will be balanced by an independent test and balance agency contracted directly by the <br /> Owner. Division 15 Section 15990 is included for reference only. <br /> 15050-6 No.99132-CP2 <br />