Laserfiche WebLink
B. Provide electrical requirements for equipment installation, connection, and control. Refer to Division 16 for <br /> exceptions. <br /> C. Provide power factor correction capacitors on motors as required to correct power factor of the motor to 90 percent <br /> or better on all motors 1 horsepower and larger. Turn capacitors over to the Electrical Contractor for installation. <br /> The power factors of motors shall be measured at rated loads. Do not provide power factor correction for motors <br /> installed with variable frequency drives. <br /> END OF SECTION 15030 <br /> 15030-5 No.99132-CP2 <br />