Rhvac-Residential&Light Commercial HVAC LoadsElite Software Development,Inc.
<br /> Rigger Heating and Cooling Wooddale 765 Boulder Dr. Revised
<br /> Andover, MN 55304 Page 2
<br /> Total Building Summary Loads
<br /> Component Area Sen Lat Sen Total
<br /> I Description Quan Loss Gain Gain Gain
<br /> 4A-6-d: Glazing-Double pane low-e (e= 0.20 or less), 88.8 2,490 0 936 936
<br /> high performance, sliding glass door, e=0.05 on
<br /> surface 2, any frame, u-value 0.33, SHGC 0.33
<br /> Andersen: Glazing-operable window, wood sash, u-value 380.6 9,386 0 9,726 9,726
<br /> 0.29, SHGC 0.32
<br /> Andersen: Glazing-operable window, wood sash, outdoor 103.9 2,564 0 3,152 3,152
<br /> insect screen with 50% coverage, u-value 0.29,
<br /> SHGC 0.32
<br /> 11N: Door-Metal - Polystyrene Core 48 1,428 0 404 404
<br /> 12F-Osw: Wall-Frame, R-21 insulation in 2 x 6 stud 1857.3 10,262 0 1,607 1,607
<br /> cavity, no board insulation, siding finish, wood studs
<br /> 15B0-10sf-8: Wall-Basement, , R-10 board insulation to 480.1 2,346 0 85 85
<br /> floor, no interior finish, 8'floor depth
<br /> 15B0-8sf-8: Wall-Basement, , R-8 board insulation to 399 2,257 0 96 96
<br /> floor, no interior finish, 8'floor depth
<br /> 15B0-10sf-4: Wall-Basement, , R-10 board insulation to 162.8 747 0 0 0
<br /> floor, no interior finish, 4'floor depth
<br /> 16B-50: Roof/Ceiling-Under Attic with Insulation on Attic 1921 3,266 0 1,844 1,844
<br /> Floor(also use for Knee Walls and Partition
<br /> Ceilings), Vented Attic, No Radiant Barrier, Dark
<br /> Asphalt Shingles or Dark Metal, Tar and Gravel or
<br /> Membrane, R-50 insulation
<br /> 21A-32: Floor-Basement, Concrete slab, any thickness, 2 1737 2,953 0 0 0
<br /> or more feet below grade, no insulation below floor,
<br /> any floor cover, shortest side of floor slab is 32'wide
<br /> 20P-30: Floor-Over open crawl space or garage, Passive, 184 547 0 52 52
<br /> R-30 blanket insulation, any cover
<br /> Subtotals for structure: 38,246 0 17,902 17,902
<br /> People: 5 1,000 1,150 2,150
<br /> Equipment: 722 7,070 7,792
<br /> Lighting: 0 0 0
<br /> Ductwork: 0 0 0 0
<br /> Infiltration: Winter CFM: 45, Summer CFM: 22 4,071 348 312 660
<br /> Ventilation: Winter CFM: 133, Summer CFM: 133 4,826 2,063 738 2,801
<br /> Exhaust: Winter CFM: 133, Summer CFM: 133
<br /> Humidification (Winter) 8.17 gal/day : 2,995 0 0 0
<br /> AED Excursion: 0 0 2,569 2,569
<br /> Total Building Load Totals: 50,138 4,133 29,741 33,874
<br /> Check Figures
<br /> Total Building Supply CFM: 1,359 CFM Per Square ft.: 0.371
<br /> Square ft. of Room Area: 3,658
<br /> Volume (ft3): 26,924
<br /> Building Loads
<br /> Total Heating Required Including Ventilation Air: 50,138 Btuh 50.138 MBH
<br /> Total Sensible Gain: 29,741 Btuh 88 ok
<br /> Total Latent Gain: 4,133 Btuh 12 %
<br /> Total Cooling Required Including Ventilation Air: 33,874 Btuh
<br /> Notes
<br /> Rhvac is an ACCA approved Manual J and Manual D computer program.
<br /> Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
<br /> All computed results are estimates as building use and weather may vary.
<br /> Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
<br /> your design conditions.