i <br /> SECTION 16140 <br /> WIRING DEVICES <br /> � <br /> 1.00 GENERAL <br /> ' A. Switches for lighting loads shall be 15 amp, 120 volt, quiet toggle type, quickwire <br /> push-in and side wired. Switches shall be ivory in color unless noted otherwise. <br /> � B. Duplex receptacles shall be 15 amp or 20 amp, 125 volt, 3 wire, grounding type <br /> quickwire push-in and side or back and side wired. Install 20 amp rated duplex <br /> receptacles in all common areas. All receptacles shall be installed with the ground slot <br /> ' down. Provide GFI receptacles where shown or required by the NEC and install with <br /> ground slot down. Receptacles shall be ivory in color unless noted otherwise. <br /> , C. Special receptacles shall be the same color and manufacturer as other devices. <br /> D. Device plates shall be provided for all receptacles and special receptacles. Device plates <br /> in finished and unfinished areas shall be plastic, ivory in color, unless noted otherwise. <br /> ' Multiple device plates shall be constructed of a single plate. No sectional plates will be <br /> accepted. <br /> , E. Switches shall be equal to the following: <br /> 1. 15 amp, 120 volt, single pole Leviton#1451-I <br /> , 2. 20 amp, 120 volt, single pole Leviton#54521-2I <br /> 3. 15 amp, 120 volt, 3-way Leviton#1453-I <br /> 4. 20 amp, 120 volt, 3-way Leviton#54523-2I <br /> 5. 15 amp, 120 volt,4-way Leviton#2654I <br /> ' 6. 20 amp, 120 volt, 4way Leviton#54529-2I <br /> 7. 20 amp, 120 volt, 2-pole Leviton#54522-2I <br /> , F. Dimmers shall be as follows: <br /> 1. 600 watt, 120 volt Lutron#NT-600 <br /> 2. 100 watt, 120 volt Lutron#NT-1000 <br /> , 3. 1,500 watt, 120 volt Lutron#NT-1500 <br /> G. Receptacles shall be equal to the following: <br /> ' 1. 15 amp, 125 volt Leviton#5320-I <br /> 2. 15 amp, 125 volt, GFT Hubbell #GF5251-I <br /> ' 3. 20 amp, 125 volt Leviton#BR20-I <br /> 4. 20 amp, 125 volt, GFT Hubbell #GF5352-I <br /> H. Special receptacles shall be equal to the following: <br /> ' 1. 20 amp, 250 volt Leviton#5821-I <br /> 2. 30 amp, 125/250 volt, 3-pole, 4-wire, grounding Leviton#278 <br /> , 3. 50 amp, 125/250 volt, 3-pole, 4-wire, grounding Leviton#279 <br /> I. Switches, receptacles and outlets shall be mounted at the following heights, measured <br /> , from device center to floor, unless noted otherwise. <br /> , RMAS CBA701 8/1/97 <br /> 061997 16140 - 1 <br /> ' <br />