B. The minimum size for wiring shall be#12 AWG copper.unless shown otherwise. All conductor ' <br /> sizes are based on copper with THWN insuladon rated at not less than 75 deg C and suitable fa <br /> wet and dry locations unless naed otherwise. , <br /> C. All circuits shall be installed using wire with 600V insulation,unless wire with a different voltage <br /> rating is indicated. The insulation,as a minimum,shall have a conductor rating of not less than ' <br /> 75 deg C in bod�wet and dry bcations. All cable shall have the same type of insulatia�by the <br /> same manufacWrer throughout the project Insulation shall meet all applicable NEMA and ICEA <br /> srandatds. . ' <br /> D. #f12 or#10 power conductors may be single strand. Control cable and all other power cable shall <br /> be stranded. ' <br /> 2.02 CONDUTfS�FITTINGS, BOXES AND DEVICES ' <br /> A The Contractar shall supply conduit,couplings,connectors,junctia�bozes,fittings and all other <br /> required items for a complete raceway system. The conduit fills indicated in the caitr�ct ' <br /> documents are based on copper conductors with THWN insuladon suirable for 75 deg C <br /> insulation in both wet and dry locadons. The Conuactor shall resize conduits for other condnctor <br /> and�or insulation syst�ems,if approvod. The conduit shall be reamed and cleaned and made free � <br /> of bun�s. Exposed conduit runs shall be straight and true with the building lines and elbows. <br /> bends and offsets shall be uniform and symmetrical. All conduit runs shall be installed with <br /> adoquate means fa drainage provided at the low points. , <br /> B. PVC Condui� <br /> 1. PVC conduit shall not be permiued. , <br /> C. Rigid Steel ConduiC ' <br /> 1. The c�dait used shsll be hot dipped galvanizcd,including the threads. Unless specified <br /> otherwise the caiduit shall not be smaller than 3/4". The condnit shall bear the U.L. ' <br /> 1sbeL <br /> 2. Job site threading�not be galvanized. However,job site thre�ing shall be painted ' <br /> with oil base primer to prevent oxidation of the threads. <br /> 3. The use�`threaciless' connecoors with rigid steel conduits is not acceptable. ' <br /> 4. Int�ermediate metal conduit st�all not be acceptable. ' <br /> D. Electric Metallic Tabing (EM'1�: <br /> 1. EMT shall not be permittsd. ' <br /> � <br /> TS-5-2-2 , <br /> , <br />