<br /> Rhvac-Residential&Light Commercial HVAC Loads Elite Software Development,Inc.
<br /> Sabre Plumbinq&Heatinq � 195 Kintyre Ln Orono
<br /> Plymouth MN 55447 Page 4
<br /> System 1 Summary Loads
<br /> Component Area Sen Lat Sen Total
<br /> Description Quan Loss Gain Gain Gain
<br /> LOW EE: Glazing-Builder Grade Low E Windows& 686.7 18,094 0 18,279 18,279
<br /> Sliding Door.33 U value .33 SHGC, u-value 0.31,
<br /> SHGC 0.29
<br /> 11J: Door-Metal- Fiberglass Core 61.8 3,151 0 1,075 1,075
<br /> EXT R-5-9': Wall-Basement, Custom, Rigid R-5 Styro- 1166 19,823 0 0 0
<br /> foam to top of footing- EXTERIOR PERIMETER-9'
<br /> basement
<br /> 12E-Obw: Wall-Frame, R-19 insulation in 2 x 6 stud 1214 7,017 0 1,189 1,189
<br /> cavity, no board insulation, brick finish,wood studs
<br /> 12E-Osw: Wall-Frame, R-19 insulation in 2 x 6 stud 3587 20,733 0 4,976 4,976
<br /> cavity, no board insulation, siding finish,wood studs
<br /> RJ 10 Spray Foam: Wall-Frame, Custom, Closed Cell 680.7 5,789 0 1,846 1,846
<br /> R10 Spray Foam
<br /> .15B0-5sf-8: Wall-Basement, , R-5 board exterior 832 5,092 0 0 0
<br /> insulation to footing, no interior finish, 8'floor depth
<br /> 16B-44: Roof/Ceiling-Under Attic with Insulation on Attic 3108.6 5,813 0 3,625 3,625
<br /> Floor(also use for Knee Walls and Partition
<br /> Ceilings), Vented Attic, No Radiant Barrier, Dark
<br /> Asphalt Shingles or Dark Metal, Tar and Gravel or
<br /> Membrane, R-44 insulation
<br /> 21A-32: Floor-Basement, Concrete slab, any thickness, 2 1747.8 2,971 0 0 0
<br /> or more feet below grade, no insulation below floor,
<br /> any floor cover, shortest side of floor slab is 32'wide
<br /> 21A-28: Floor-Basement, Concrete slab, any thickness, 2 813.8 1,522 0 0 0
<br /> or more feet below grade, no insulation below floor,
<br /> any floor cover, shortest side of floor slab is 28'wide
<br /> 20P-30: Floor-Over open crawl space or garage, Passive, 186.2 553 0 85 85
<br /> R-30 blanket insulation, any cover
<br /> 20P-38: Floor-Over open crawl space or garage, Passive, 410.7 1,047 0 160 160
<br /> R-38 blanket insulation,any cover_ _
<br /> Subtotals for structure: 91,605 0 31,235 31,235
<br /> People: 6 1,200 1,380 2,580
<br /> Equipment: 683 3,430 4,113
<br /> Lighting: 0 0 0
<br /> Ductwork: 5,258 1,447 1,614 3,062
<br /> Infiltration: Winter CFM: 166, Summer CFM: 0 15,072 0 0 0
<br /> Ventilation: Winter CFM: 140, Summer CFM: 140 5,080 3,547 1,076 4,623
<br /> AED Excursion: 0 0 702 702
<br /> System 1 Load Totals: 117,015 6,877 39,437 46,314
<br /> Check Fi ures
<br /> Supply CFM: 1,797 CFM Per Square ft.: 0.272
<br /> Square ft. of Room Area: 6,605 Square ft. Per Ton: 1,711
<br /> Volume (ft') of Cond. Space: 68,510
<br /> S stem Loads
<br /> Total Heating Required Including Ventilation Air: 117,015 Btuh 117.015 MBH
<br /> Total Sensible Gain: 39,437 Btuh 85 %
<br /> Total Latent Gain: 6,877 Btuh 15 %
<br /> Total Cooling Required Including Ventilation Air: 46,314 Btuh 3.86 Tons (Based On Sensible+ Latent)
<br /> Notes
<br /> Rhvac is an ACCA approved Manual J and Manual D computer program.
<br /> Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
<br /> All computed results are estimates as building use and weather may vary.
<br /> Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
<br /> your design conditions.
<br /> C:\...\Gonyea 195 Kintrye Ln Orono SIMPSON.rh9 Monday, June 30, 2014, 10:56 AM