Laserfiche WebLink
+ � l <br /> � . ' . . . - Duct Sensor Location Considerations: <br /> l. Proper duct smoke detection location must ensure ' <br /> /Exhaust Damper senso�oK adequate airflow within the duct housing. <br /> � 2. Duct air velocity rating is 300 to 4000 ft/min(91 to <br /> Exnaust•- ' �Retum Air 1220 m/min).Pressure differential between intake ' <br /> and exhaust tubes is required to be between 0.015 to <br /> 0o not iocate; 1.55 inches of water(0.381 to 39.37 mm). <br /> se�sor nere � 3. Ensure accessibility for test and service. <br /> Rda per r � 4. Proper Locations:downstream side of filters to detect <br /> fires in the filters;in return ducts,ahead of mixing <br /> ; areas;upstream of air humidifier and cooling coil. <br /> 5. Other locations and orientations may be required for <br /> Fresh air—► ;�—►Supply Air proper duct smoke detection depending on duct <br /> access,system design,and duct airflow testing. <br /> o,noc�ocate Filter bank sensor otc Contact your local Simplex product supplier for <br /> sensor here 3SSiSt3IICC. <br /> Locations to Avoid: <br /> Additional lnformation.Refer to NFPA 90A,Standard 1. Where dampers closed for comfort control would <br /> for the Installation of.4ir Conditioning and Yentilating interfere with airflow. <br /> Systems;NFPA 72,the National Fire Alarm and Signaling 2, Next to outside air inlets(unless the intent is ta <br /> Code;and the NEMA Guide for Proper Use of Smoke monitor smoke entry from that area). <br /> Detectors in Duct Applications,and Installarion Instrucrions 3. In retum air damper branch ducts and mixing areas <br /> 574-776. where airflow may be restricted. <br /> . - . . <br /> Generaf Mechanica{and Environmental <br /> Air Velocity Range(tinear ff/min) 300 to 4000 ft/min(91 to 1220 mlmin) <br /> Sensor Sensitivity Range 0.2%to 3.7°k per foot of obscuration,selectable at hast control panel <br /> UL Listed Temperature Range 32°F to 100°F(0°C to 38°C) � <br /> Operating Temperature Range 32°F to 122°F(0°C to 50°C) <br /> Storage Temperature Range 0°F to 140°F(-78°C to 60°C) . <br /> Humidity Range 10%to 95%RH,non-condensing <br /> Wiring Connections Terminal blocks,18 to 12 AWG(0.82 mmz to 3.31 mm2) <br /> Housing Color Black base with clear cover <br /> Remote StatuslAlarm LED and Test Station with Remate Status/Alarm LED <br /> Remote Alarm LED Current 1.2 mA,no impact to 24 VDC alarm current(2098-9808 or 2098-9806) <br /> Test Station Keyswitch Curcent 3.3 mA,no impact to 24 VDC alarm current(2098-9806} <br /> Remote Alarm LED and Test Station Distance 250 ft(76 m)maximum <br /> Addressable Operation <br /> Data Communications IDNet or MAPNET 11 communications,autaselect,one address per housing; <br /> provides operating power to mode14098-9755 <br /> Model 4098-9756 with Supervised Multiple Relay Control,Requires Separate Fused 24 VDC from Fire Atarm Power Supply <br /> lnput Voltage 1&32 VDC(24 VDC nomina!) <br /> Standby Current 3 mA @ 24 VDC <br /> Alarm Current 15 mA @ 24 VDC;add 15 mA for each 409&9843 relay <br /> For use with 409&9843 relay only,quantity of 15 maximum;distance of 500 ft <br /> Supervised Remote Relay Control Output (152 m)maximum;requires 4081-9008(ref.733-894)10 ki2, 1/2 W end-of-line <br /> resistor <br /> 4098-9843 Relay Output Ratings,Single Form C,use with Modet 4Q9&9756 Only <br /> Coil Current 15 mA @ 24 VDC,up to t5 maximum per relay control oufput <br /> Relay Contacts 7 A at 0.35 PF @ 28 VDC&120 VAC;250µA @ 5 VDC <br /> Location Distance 500 ft(152 m)maximum to relay coils;locate relays within 3 ft(1 m)of device <br /> being controlled per NFPA 72 <br /> TYCO,SJMPLEX,and the product names listed in tlds materia!are marks and/or registered mrrrLa�.Unauthorized rere is srricHy prohibited..NFPA 72 and 7Jatinnaf Fve A(arm and <br /> Signa/ing Corle are registered trademarl�of the National Fire Protection Association(IJFPA): <br /> ��S i m p I Ex Tyco Fire Profection Products• Westminster,MA•01441-0001•USA 54098-0030-9 11 t2012 <br /> www.simplexgrinnelLcom <br /> O 2012 Tyw F'ue Prvtec7ion Products.All rightr resernd AUspecificaiinns wtd ather injormation shoxm xrre avrent as afdaument rnvision dat¢m�d m�e suhject ta chanbse wrthout notice. . <br />