rods,ground rod splices,and lightning protection system as indicated,All materials used(molds, <br /> welding metal,tools,etc.)shall be by"cadweld"and installed per manufacturer's <br /> recommendation and procedures: <br /> b. All above grade or interior grounding and bonding conductors shall be reconnected by o e hole <br /> crimp type(compression)connections for#6 AWG bare copper conductor,and two hole rimp <br /> type(compression)connections for #2 AWG bare copper conductor and larger.Mechan cal <br /> connections,fitting or connections that depend solely on solder shall not be used.AC se ice <br /> electrical ground shall be sized per the NEC with#2 AWG solid tinned copper wire m' ' um. <br /> Service ground wire shall be continuos run in an unbroken manner. <br /> c: Ground Rods - <br /> All ground rods shall be 5/8"diameter x 10'-0"long Copperweld"or approved equal,and s all be of <br /> the number aad at locations indicated on the drawings.Ground rods shall be driven full len <br /> vertical in undisturbed earth.All ground rods to be 8' apart unless otherwise noted. <br /> d. Ground Bars <br /> All ground bars shall be '/."thick bare copper plate and of size indicated on drawings. <br /> e. Cables <br /> All ground cable shall be standard tinned copper and of size indicated on drawings.The type of cable <br /> shall be as follows: ' ' <br /> Cable Size Cable Type Use of Cable <br /> #2/0 AWG Stranded To main ground,i.e.,building <br /> steel,cold water pipe,or <br /> existing ground rod,and for <br /> ' all lightning protection <br /> #6 AWG Stranded Grounding of Antenna Cables <br /> #2 AWG Stranded Green Insulated Indoor Halo Ring <br /> #2 AWG Solid Solid Outdoor Ring Grounds, <br /> and all equipment,poles and <br /> towers <br /> f. Cable Tray <br /> Ground all sections of the cable tray as indicated on the drawings. <br /> END OF SECTION <br /> CNS/[JS WEST COMMUNICATIONS ELECTRICAL MATERIALS AND THODS <br /> SIvIMA NO.96419.16 16000-4 17 DEC.96 <br />