Laserfiche WebLink
Performance Guarantees <br /> Subject to the terms and conditions of the contract documents, <br /> SEH D�B hereby guarantees that, following a complete rehabilitation <br /> procedure, the tanks included under this contract will for the term of <br /> the contract: <br /> 1. Be in general compliance regarding safery and access with the <br /> following industry standards: <br /> • American Water Works Association (AWWA) Standards <br /> (D100 & D102) <br /> • Occupational Safety and Health Administration (OSHA) <br /> Article 1910 <br /> 2. Be maintained to meet or exceed the following industry <br /> performance levels for coating systems: <br /> • For exterior polyurethane systems: SSPC Paint Specification 36 <br /> -Performance Level 3. <br /> 3. For all other coating systems: <br /> • Rusting:ASTM D-610-Grade 9 <br /> • Cracking: None Allowed <br /> • Peeling: None Allo�ved <br /> • Delimitation: None Allowed <br /> • Pitting: None Allowed <br /> All compliance with these specifications will be verified by our certified <br /> coatings inspectors. <br /> Our SEH D�B inspectors are licensed Professional Engineers in the <br /> State of Minnesota, Certified Coating Inspectors through the National <br /> Association of Corrosion Engineers (NACE) and Certified Weld <br /> Inspector (CWI) through the American Welding Society. <br /> � <br /> performance guarantees � page 17 <br />