Inspection Report No.14033 •:gle Fire Protection Co. Page 3 <br />Report 'TO:MACMILLAN TENNIS <br />---•;------------------------------------------------- <br />15. See Control Valve Maintenance Table <br />CONTROL VALVE MAINTENANCE _'ABLE <br />CONTROL VALVES NO. <br />TYPE OPEN <br />City Conn. Control <br />Tank Control <br />Pump Control <br />Sectional Control <br />System Control 2 <br />0 . S . Y YES <br />Other Control <br />16. Water Flow Test at <br />Sprinkler Riser <br />WATER SUPPLY SOURCE: <br />CITY <br />DATE <br />TEST PIPE <br />LOCATION <br />List Water <br />Flow Test <br />This Water <br />Flow Test 4/ 25/ 89 <br />RISER <br />17. Explain a% "NO" answers and comments: <br />EXPLAIN <br />ABNORMAL <br />SECURED CLOSED SIGNS CONDITION <br />NO NO YES <br />TANK PUMP <br />SIZE OF STATIC RESIDUAL <br />TEST PIPE PRESSURE PRESSURE <br />2 " 80 80 <br />18. Adjustments or corrections made during this inspection: <br />19. Althe these comments are not the result of an engineering review, the <br />foll, g desirable improvements are recommended: WIRE AIR SWITCH ON <br />PRESSIG,,,E TANK TO CENTRAL STATION. WIRE ALARM SWITCH ON DRY VALVE. INSTALL <br />LOW AIR SWITCH ON DRY VALVE. <br />Inspector's Signature: Date: <br />