15,100.6. MOTOR AND _CABLE: Each pump motor shall he a sealed submersible <br />type either air -filled or� running in high dielectric oil. Motors shall be <br />,.. NEMA Design B with stator winding and stator leads insulated with moisture <br />resistant Class F insulation or approved oqu al. Motors shall be designed for <br />continuous operation in a totally, partially or non -submerged condition. <br />•+ Motors shall be capable of sustaining a minimum of 10 starts per hour. <br />The pump motor cable, installed, shall he suitable for submersible pump appli- <br />cation with P122-MSHA approval and this shall he indicated by a code or legend <br />r+ permanently embossed on the cable. Cable sizing shall conform to NEC specifi- <br />cations for pump motors and shall be of adequate size to allow motor voltage <br />conversion without replacing cable. Pump cable shall be continuous from pump <br />to the control panel. Junction boxes in the pump chamber are not allowed. <br />The cable entry into the pump motor housing shall be protectea by a minimum of <br />two sealing systems; one the cable entry into the junction chamber and the <br />second sealing the junction chamber from the motor. The cable entry water <br />sgai design shall be such that it p cludes specific torque requirements to <br />insure a watertight and submersible seal. The junction chamber and motor <br />shall be separated by a stator lead scaling gland or terminal board which <br />shall isolate the motor interior from foreign materials gaining access through <br />the pump top. <br />f4 Each unit shall be provided with an adegt.iately designed cooling system. Ther- <br />mal radiators integral to the stator housing, cast in one unit are acceptable <br />for small motors. Units having large motors shall be provided with water <br />jackets alone or in conjunction with thermal radiators and separate circula- <br />�a Lion. Water jacket cooling channels and ports shall he non -clogging by virtue <br />of their dimensions and connections for external flushing shall be provided. <br />`s Each unit shall be capable of continuous operation under full load without <br />damage for extended periods with only the pump volute immersed in the pumped <br />media. Before final acceptance, a field running test demonstrating this <br />abilitv, with 24 hours of continuous operation under the above conditions, <br />!; shall he performed for all pumps being supplied if required ')v the Engineer. <br />to <br />integral thermal sensors shall he provided on all units with a water jacket or <br />9.4 HP and over to monitor stator temperatures. There %hall he one for each <br />phase group in the motor. These shall he used in conjunction with and a sup- <br />plement to the motor over current protection provided at the c,)ntrol panel.. <br />" All units of 100 HP or more shall he furnished with a moisture sensor and <br />it thermal sensors monitoring hearing temperatures in addition to the motor <br />thermal sensors described above. Moisture and bearing thermal sensore, shall <br />be independent of the motor sensors and shall be used in conjunction with and <br />a supplement to the motor over current protection provided at the control <br />panel. <br />35,ton-5 <br />�-5R41 c <br />C'Jpvright 198% <br />anne5froo, Ro%ene, AndNrlik <br />t� Asxof ist••y, Inc. <br />