0 <br /> Exception:Tank vehicles where the operator carries and can utilize a remote emergency shutoff device which, <br /> when activated, immediately causes flow of fuel from the tank vehicle to cease. <br /> o Persons responsible for dispensing operations shall be trained in the appropriate mitigating actions in the event <br /> of a fire, leak or spill. Training records shall be maintained by the dispensing company and shall be made <br /> available to the code enforcement official upon request. <br /> o Operators of tank vehicles used for mobile fueling operations shall have in their possession at all times an <br /> emergency communications device to notify the proper authorities in the event of an emergency. <br /> o The tank vehicle dispensing equipment shall be constantly attended and operated only by designated personnel <br /> who are trained to handle and dispense motor fuels. <br /> o Prior to beginning dispensing operations, precautions shall be taken to ensure ignition sources are not present. <br /> o The engines of vehicles being fueled shall be shut off during dispensing operations. <br /> o No night time fueling (dusk to dawn) <br /> o The dispensing hose shall be properly placed on an approved reel and shall be positioned with respect to boats <br /> being fueled to prevent foot and/or boat traffic from going over the delivery hose. <br /> o The code enforcement official and other appropriate authorities shall be notified when a reportable spill or <br /> unauthorized discharge occurs. A reportable spill is anything over 2 gallons. <br /> o This tank will only be used to fuel boats that are in the water. No fueling shall take place to boats or vehicles in <br /> the parking area. <br /> o General fire safety regulations for marine motor fuel-dispensing facilities shall comply with Sections 2210.5.1 <br /> through 2210.5.7 of the Minnesota State Fire Code <br /> o A placard shall be installed near the hose reel listing these restrictions. <br /> o Any building on site of this fueling operation that has a fire suppression system shall be current on their <br /> inspections of that system and a fire inspection done on the premises before the permit is approved. All <br /> violations of the fire code will need to be corrected in a timely fashion or the permit will be revoked. <br /> Required prior to issuance of permit. <br /> 1- Detailed site plan <br /> 2- Tank certification and specs <br /> 3- Proof of training <br /> Contact us if you have questions. <br /> Lyle Oman <br /> Building Official <br /> City of Orono <br /> TO SCHEDULE AN INSPECTION, CALL: 952.249.4600 <br /> 2 <br />