Laserfiche WebLink
202-202 STAIRS-HALL <br /> j I 1 McGUIRE RESIDENCE <br /> HEAT LOSS AND GAIN CALCULATIONS FOR INDIVIDUAL SPACES <br /> ROOM: 1201/202 STAIRS/HALL 1 j HEIGHT: 8.5 <br /> FLOOR 1 2� j AREA: 288 VOLUME: 2,448 <br /> OCCUPANTS: 0 1 j <br /> 1 IHEAT LOSS <br /> ELEMENT AREA X 'MULTIPLIER 1= 'BTU/HR <br /> ROOF 1 288 IS.F 2.21Btu/Hr/S.F' 634 <br /> DOORS j 0 " 57 " i - <br /> WINDOWS 35 1 57; " 1 1,9951 <br /> WALLS 1 101 " j 51 " 1 505 <br /> FOUNDATION 0 1 7.51 " 1 - <br /> INFILTRATION* 10 ICFM 1 102.6 Btu/Hr/CFM 1,047 1 <br /> (TOTAL: 4,180 <br /> VENTILATION** 0 CFM 102.6JBtu/Hr/CFM j - <br /> 1 I I I TOTAL 4,180 <br /> I I 1 <br /> ! ! HEAT GAIN ;SENS. LATENT TOTAL <br /> ROOF 288 S.F. 0.92!Btu/Hr/S.F. j 265 265 <br /> DOORS !S&W j 0 " j 1001 " - - <br /> DOORS 1N&E 1 0 " 91 " - 1 - <br /> WINDOWS S&W 1 35 i" ' 1001 " I 3,500 3,500 <br /> WINDOWS N 0 " 91 " 1 - ! 1 - <br /> WINDOWS E 0 601 " 1 + - ! - <br /> WALLS 1 S&W 101 1 1.91 " 192 1 1 192 <br /> WALLS N 0 i" 1 0.81 " 1 - i - <br /> WALLS ,E 0 1 O.Si " - - <br /> i <br /> LIGHTS 1 1 0 " 3.4151*** j - - <br /> EQUIPMENT 0 1KW 34151Btu/kw jI - - <br /> j <br /> OCCUPANTS i 0 **** 300/3001 1 - - - <br /> INFILTRATION 10 jCFM 16/25iBtu/hr/CFM 163 255 418 <br /> 1 1 TOTAL: 4,120 j 255 4,375 <br /> VENTILATION 0 (CFM 16/25iBtu/hr/CFM - - - <br /> • 1TOTAL: 4,120 255 I 4,375 <br /> NOTES: <br /> Infiltration based on 1/4 air changes per hour <br /> *** Lighting heat gain based on 1 watt per square foot <br /> **Ventilation based on 2 CFM per S.F. Bathroom or Laundry 1 1 <br /> ****Occupants normally in continuous use of area <br /> *****Sensible and Latent load- based on light activity unless noted otherwisei <br /> Page 1 <br />