Laserfiche WebLink
104 LIBRARY <br /> McGUIRE RESIDENCE , j I <br /> HEAT LOSS AND GAIN CALCULATIONS FOR INDIVIDUAL SPACES I <br /> ROOM: 104 LIBRARY HEIGHT: 8.5 <br /> FLOOR 1 ;AREA: I 432 ,VOLUME:I 3,672 <br /> OCCUPANTS: I 1 1 <br /> I (HEAT LOSS <br /> ELEMENT AREA I X MULTIPLIER = BTU/HR <br /> ROOF 1 0 S.F 2.21Btu/Hr/S.F - I <br /> DOORS I 0 " 57 " - <br /> WINDOWS 70 ," 57 " 1 3 ,990 f <br /> WALLS I I 151 1 5 " I 755 <br /> FOUNDATION 0 I 7.5, " I - <br /> INFILTRATION* 15 CFM 102.6 Btu/Hr/CFM 1,570 <br /> VENTILATION** 20 CFM 102.6 Btu/Hr/CFM 2,052 <br /> ;TOTAL 8,367 <br /> 1 HEAT GAIN SENS. LATENT TOTAL <br /> ROOF 0 S.F.j0.92 Btu/Hr/S.F. - - <br /> DOORS S&W 0 " 100 " 1 I - - <br /> DOORS N&E 0 I" 9 I [ I - 1 I - <br /> WINDOWS S&W 0 100 " - - <br /> WINDOWS N 70 I" 9 " 1 630 630 <br /> WINDOWS E 0 601 - i - <br /> WALLS S&W 0 " 1.9 " - <br /> WALLS N 151 I" 0.8 " j 121 j 121 <br /> WALLS 1E 0 1 0.81 " T - 1 - <br /> LIGHTS I 432 " 3.4151*** 1,475 i 1,475 <br /> EQUIPMENT 0 KW I 34151Btu/kw - ( - <br /> OCCUPANTS 1 i* ••' ' 300/3001 300 300 I 600 <br /> INFILTRATION ! 15 1CFH 16/251Btu/hr/CFM 245 383 627 <br /> VENTILATION 20 1CFM 1 16/2518tu/hr/CFM 320 500 820 <br /> I i TOTAL: I 3,091 I 1,183I 4,273 <br /> NOTES: <br /> f <br /> Infiltration based on 1/4 air changes per hour I , <br /> ***Lighting heat gain based on 1 watt per square foot 1 <br /> **Ventilation based on 2 CFM per S.F. Bathroom or Laundry <br /> —*Occupants normally in continuous use of area ! 1 <br /> Sensible and Latent load-based on light activity unless noted otherwise; I <br /> Page 1 <br />