12107/2001 08:12 6127845236 CHETS SHOES PAGE 06 <br /> SFNM Fact Sheet INS-FACT 1999-11 <br /> November 1, 1999 <br /> Page 2 of 4 <br /> posts not less than 3 feet above the ground,and(5)located not less than 5 feet from the <br /> tank. <br /> 7. Dispensers shall be protected against physical damage from vehicles by mounting on a cotcrete <br /> island 6 inches or more in height or by other approved means. <br /> 8. There shall be an emergency shut-off device located between 20 feet and 100 feet from the dispenser. <br /> Activation of the emergency shut-off shall shut down transfer of fuel to the dispenser and shall close <br /> all valves that supply fuel to the dispenser.The emergency shut-off shall be distinctly labeled <br /> EMERGENCY FUEL SHUTDOWN DEVICE. <br /> 9. Within 75 feet of the dispenser,there shall be a portable fire extinguisher rated at a minimum 2-A, <br /> 20-B-C. The fire extinguisher shall be inspected annually by qualified personnel. <br /> 10. Signs prohibiting smoking, dispensing into unapproved containers, and requiring vehicle engines to <br /> be stopped during fueling shall be conspicuously posted within sight of each dispenser.When open to <br /> the public or when there are employees that are under 16 years old, there shall be a sign stating the <br /> minimum age to dispense flammable/combustible liquids is 16. <br /> 11. Weeds, grass,brush, trash and other combustible materials shall!sept at least 10 feet from an AST. <br /> 12. ASTs shall have a minimum 3-foot separation between tanks. Larger tanks may require more space. <br /> 13. Storage vessels for LP-gas and'CNG shall be located 20 feet or more from AST's. Suitable means <br /> shall be provided to prevent the accumulation of liquids under adjacent LP-gas containers such as by <br /> dikes, diversion curbs or gradiztg.When AST's are within a diked area, the LP-gas containers shall be <br /> outside the diked area and at least 10 feet-away from the centerline of the wall or the diked area. <br /> 14. ASTs shall have warning signs or labels to identify the tank contents to emergency personnel. <br /> 15. ASTs require normal and emergency vents. The normal vent shall terminate at least 12 feet above the <br /> ground level and 5 feet from building openings or property lines that can built upon. <br /> 16. Electrical equipment shall be installed in accordance with the Minnesota State Electrical Code. <br /> 17. Dispensing is required to be under the supervision of a qualified attendant at all times. The attendants <br /> primary function shall be to supervise, observe and control the dispensing of motor fuels.The <br /> attendant shall prevent the dispensing of flammable and combustible liquids and flammable gases <br /> into containers not in compliance with the Minnesota Uniform Fire Code. The attendant shall also <br /> control sources of ignition, give immediate attention to accidental spills or releases,and be prepared <br /> to use fire extinguishers. A method of communicating with the flute department shall be provided for <br /> the attendant. <br /> 18. Contact the State Fire Marshal Division for requirements that may apply to situations such as: <br /> • Dispensing at a bulk plant,marina or resort • Dispensing of LPG,CNG, etc. <br /> • Dispensing inside a building • Dispensing from tank vehicles <br /> • Dispensing into containers • Unsupervised dispensing <br /> 19. Pages 3 and 4 of this information sheet contain additional requirements specific to the type of above <br /> ground tank installation used for dispensing. <br />