Rhvac-Residential&Light Commercial HVAC Loads Elite Software Development,Inc
<br /> Sabre Plumbing&Heating4)" SHIELDS-364 West Lake St Orono
<br /> Plymouth,MN 55447 Page 5
<br /> System 2 Summary Loads
<br /> C p0 nen t Area Sell Sen
<br /> DescriptionQuan Loss Gain el
<br /> ' Gan Gain
<br /> LDK LOW EE: Glazing-Low EE Windows&Sliding Door 794.5 20,264 0 20,600 20,600
<br /> .30 U value .34 SHGC, u-value 0.3, SHGC 0.34
<br /> 11G: Door-Wood - Panel 48 2,203 0 674 674
<br /> 11J: Door-Metal - Fiberglass Core 24 1,224 0 374 374
<br /> 12E-Obw: Wall-Frame, R-19 insulation in 2 x 6 stud 1034.9 5,982 0 802 802
<br /> cavity, no board insulation, brick finish, wood studs
<br /> 15A-10sffc-8: Wall-Basement, concrete block wall, R-10 347.4 1,328 0 30 30
<br /> foam board to floor, no framing, no interior finish,
<br /> filled core, 8'floor depth
<br /> RJ R13 Closed Cell: Wall-Frame, Custom, Spray Foam R- 657.5 4,246 0 870 870
<br /> 13
<br /> EXT R-10: Wall-Basement, Custom, Styrofoam to top of 724 6,153 0 0 0
<br /> footing- EXTERIOR PERIMETER-9' Basement
<br /> 12E-Osw: Wall-Frame, R-19 insulation in 2 x 6 stud 1760.2 10,173 0 2,083 2,083
<br /> cavity, no board insulation, siding finish, wood studs
<br /> 16B-50: Roof/Ceiling-Under Attic with Insulation on Attic 3252.1 5,529 0 3,252 3,252
<br /> Floor(also use for Knee Walls and Partition
<br /> Ceilings), Vented Attic, No Radiant Barrier, Dark
<br /> Asphalt Shingles or Dark Metal, Tar and Gravel or
<br /> Membrane, R-50 insulation
<br /> 21A-20: Floor-Basement, Concrete slab, any thickness, 2 3252.1 7,463 0 0 0
<br /> or more feet below grade, no insulation below floor,
<br /> any floor cover, shortest side of floor slab is 20'wide
<br /> Subtotals for structure: 64,565 0 28,685 28,685
<br /> People: 6 1,200 1,380 2,580
<br /> Equipment: 683 4,130 4,813
<br /> Lighting: 0 0 0
<br /> Ductwork: 3,128 754 906 1,660
<br /> Infiltration: Winter CFM: 142, Summer CFM: 0 12,913 0 0 0
<br /> Ventilation: Winter CFM: 280, Summer CFM: 280 10,160 5,896 1,793 7,689
<br /> Humidification (Winter) 28.87 gal/day : 10,589 0 0 0
<br /> AED Excursion: 0 0 926 926
<br /> System 2 Load Totals: 101,355 8,534 37,820 46,354
<br /> Check Figures �_.:,
<br /> Supply CFM: 1,688 CFM Per Square ft.: 0.260
<br /> Square ft. of Room Area: 6,504 Square ft. Per Ton: 1,684
<br /> Volume (ft')of Cond. Space: 61,246
<br /> System Loads
<br /> Total Heating Required Including Ventilation Air: 101,355 Btuh 101.355 MBH
<br /> Total Sensible Gain: 37,820 Btuh 82
<br /> Total Latent Gain: 8,534 Btuh 18 %
<br /> Total Cooling Required Including Ventilation Air: 46,354 Btuh 3.86 Tons(Based On Sensible + Latent)
<br /> 1 Notes _ II
<br /> Rhvac is an ACCA approved Manual J and Manual D computer program.
<br /> Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
<br /> All computed results are estimates as building use and weather may vary.
<br /> Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
<br /> your design conditions.
<br /> C:\ ...\LDK 364 West lake St Orono SHIELDS.rh9 Monday, February 17, 2014, 2:02 PM