<br /> Rhvac-Residential&Light Commercial HVAC Loads Elite Software Development,Inc.
<br /> Sabre Plumbing&Heating SHIELDS-364 West Lake St Orono
<br /> Plymouth MN 55447 -__ Page 4
<br /> System 1 Summary Loads
<br /> Component Area Sen Lat Sen Total
<br /> I Description Quell Loss Gain`' - Gain Gain
<br /> LDK LOW EE: Glazing-Low EE Windows & Sliding Door 332.8 8,489 0 9,766 9,766
<br /> .30 U value .34 SHGC, u-value 0.3, SHGC 0.34
<br /> 12E-Obw: Wall-Frame, R-19 insulation in 2 x 6 stud 346.1 2,000 0 339 339
<br /> cavity, no board insulation, brick finish, wood studs
<br /> EXT R-10: Wall-Basement, Custom, Styrofoam to top of 518.3 4,406 0 0 0
<br /> footing- EXTERIOR PERIMETER-9' Basement
<br /> RJ R13 Closed Cell: Wall-Frame, Custom, Spray Foam R- 216 1,396 0 334 334
<br /> 13
<br /> 12E-Osw: Wall-Frame, R-19 insulation in 2 x 6 stud 926.7 5,357 0 1,285 1,285
<br /> cavity, no board insulation, siding finish, wood studs
<br /> 16B-50: Roof/Ceiling-Under Attic with Insulation on Attic 1247.8 2,121 0 1,323 1,323
<br /> Floor(also use for Knee Walls and Partition
<br /> Ceilings), Vented Attic, No Radiant Barrier, Dark
<br /> Asphalt Shingles or Dark Metal, Tar and Gravel or
<br /> Membrane, R-50 insulation
<br /> 21A-20: Floor-Basement, Concrete slab, any thickness, 2 1247.8 2,864 0 0 0
<br /> or more feet below grade, no insulation below floor,
<br /> any floor cover, shortest side of floor slab is 20'wide
<br /> Subtotals for structure: 26,633 0 13,047 13,047
<br /> People: 4 800 920 1,720
<br /> Equipment: 0 478 478
<br /> Lighting: 0 0 0
<br /> Ductwork: 0 0 0 0
<br /> Infiltration: Winter CFM: 0, Summer CFM: 0 0 0 0 0
<br /> Ventilation: Winter CFM: 280, Summer CFM: 280 10,160 7,094 2,152 9,245
<br /> Humidification (Winter) 17.87 gal/day : 6,554 0 0 0
<br /> AED Excursion: 0 0 2,013 2,013
<br /> System 1 Load Totals: 43,347 7,894 18,610 26,504
<br /> i Check Figures _._ 3
<br /> Supply CFM: 771 CFM Per Square ft.: 0.309
<br /> Square ft. of Room Area: 2,496 Square ft. Per Ton: 1,130
<br /> Volume (ft3)of Cond. Space: 23,501
<br /> System Loads -._.. _�_...... T
<br /> Total Heating Required Including Ventilation Air: 43,347 Btuh 43.347 MBH
<br /> Total Sensible Gain: 18,610 Btuh 70
<br /> Total Latent Gain: 7,894 Btuh 30
<br /> Total Cooling Required Including Ventilation Air: 26,504 Btuh 2.21 Tons(Based On Sensible + Latent)
<br /> Notes ,
<br /> Rhvac is an ACCA approved Manual J and Manual D computer program.
<br /> Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
<br /> All computed results are estimates as building use and weather may vary.
<br /> Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
<br /> your design conditions.
<br /> SHIELDS.rh9 Monday, February17, 2014, 2:02 PM