RHVAC-Residential&Light Commercial HVAC Loads Program Elite Software Development,Inc.
<br /> Differ,Inc. Patina
<br /> Hamel,MN 55340-9691 Page 3
<br /> Total Building Summary Loads
<br /> Component Area Sen. Lat. Sen. Total
<br /> Description Quan Loss Gain Gain Gain
<br /> 3A Window Double Pane Clear Glass Wood Frame 468 23,725 0 20,700 20,700
<br /> 8M Glass Door Double Clear Glass Wood Frame 42 2,129 0 1,932 1,932
<br /> 10F Door Wood Solid Core&Metal Storm 42 1,236 0 318 318
<br /> 12D Wall R-11 + 1/2"Asphlt Board(R-1.3) 4,336 31,913 0 8,186 8,186
<br /> 16H Ceiling R-38 Insulation 2,040 4,880 0 2,334 2,334
<br /> 21A Basemt Floor 2'or More Below Grade 2,040 4,504 0 0 0
<br /> Subtotals for structure: 8,968 68,387 0 33,470 33,470
<br /> Active People: 6 0 1,380 1,800 3,180
<br /> Inactive People: 0 0 0 0 0
<br /> Appliances: 0 0 0 1,200 1,200
<br /> Lighting: 0 0 0
<br /> Ductwork: 0 0 0 0 0
<br /> Infiltration:Winter CFM: 618.8, Summer CFM: 442.0 552 60,758 10,496 9,435 19,931
<br /> Ventilation:Winter CFM: 75.0, Summer CFM: 75.0 0 7,364 1,781 1,601 3,382
<br /> Sensible Gain Total: 47,506
<br /> Temperature Swing Multiplier: X1.00
<br /> Building Load Totals: 136,50 13,657 47,506 61,163
<br /> 9
<br /> Check Figures
<br /> Total Building Supply CFM: 1000 CFM per square foot: 0.49
<br /> Square feet of room area: 2,040 Square feet per ton: 396.785
<br /> Building Loads
<br /> Total heating required with outside air: 136,509 Btuh 136.509 MBH
<br /> Total sensible gain: 47,506 Btuh 78 %
<br /> Total latent gain: 13,657 Btuh 22 %
<br /> Total cooling required with outside air: 61,163 Btuh 5.097 Tons(based on sensible+ latent)
<br /> 5.141 Tons(based on 77%sensible capacity)
<br /> Notes
<br /> Calculations are based on 7th edition of ACCA Manual J.
<br /> All computed results are estimates as building use and weather may vary.
<br /> Be sure to select a unit that meets both sensible and latent loads.
<br /> I
<br /> Tuesday,June 18,2002