Laserfiche WebLink
Document management portal powered by Laserfiche WebLink 9 © 1998-2015 Laserfiche. All rights reserved.
RHVAC-Residential;& Light Commercial HVAC Loads Elite Software Development, Inc. <br /> Program <br /> Detter. Inc Patinai <br /> I <br /> Project: Patina Company: Differ Cooling and Heating <br /> Client: Kathrine Patina Representative: Doug Bjork <br /> Address: 280 Wakefield Rd Address: 820 Tower Drive <br /> City: Wayzata,Mn City: Medina,MN.55340 <br /> Phone: Phone: (763)-478-8558 <br /> Fax: Fax: (763)-478-2426 <br /> Comment: <br /> Design Data <br /> Project Name: Patina <br /> Reference City: Minneapolis,Minnesota <br /> Daily Temperature Range: Medium <br /> Latitude: 44 Degrees <br /> Elevation: 834 Feet <br /> Elevation Sensible Adj.Factor: 1.000 <br /> Elevation Total Adj.Factor: 1.000 <br /> Outdoor Outdoor Indoor Indoor Grains <br /> Dry Bulb Wet Bulb Rel.Hum. Dry Bulb Difference <br /> Winter: -20 N/A WA 72 WA <br /> Summer. 95 75 50% 75 36 <br /> Check Figures — <br /> Total Building Supply CFM: 1000 CFM per square foot: 0.49 <br /> Square feet of room area: 2,040 Square feet per ton: 396.785 <br /> Building Loads <br /> Total heating required with outside air: 136,509 Btuh 136.509 MBH <br /> Total sensible gain: 47,506 Btuh 78 % <br /> Total latent gain: 13,657 Btuh 22 % <br /> Total cooling required with outside air: 61,163 Btuh 5.097 Tons(based on sensible+latent) <br /> 5.141 Tons(based on 77%sensible capacity) <br /> Notes <br /> Calculations are based on 7th edition of ACCA Manual J. <br /> All computed results are estimates as building use and weather may vary. <br /> Be sure to select a unit that meets both sensible and latent loads. <br /> I <br /> I <br /> Tuesday,June 18,2002 <br />