Laserfiche WebLink
. y II <br /> Nova Industries Inc. <br /> Report No.:TJ1409 <br /> July 23,2013 <br /> Page 2 of 3 <br /> E 84 TEST DATA SHEET: <br /> CLIENT: Nova Industries DATE: July 1, 2013 <br /> SAMPLE: Duct Armor <br /> FLAME SPREAD: <br /> IGNITION: 3 Min. and 3 Sec. <br /> FLAME FRONT: 4 feet maximum <br /> TIME TO MAXIMUM FLAME SPREAD: 4 feet at 6 minutes <br /> TEST DURATION: 10 minutes <br /> SUMMARY: FLAME SPREAD: 10 @ 10:00 SMOKE DEVELOPED: 30 @110:00 <br /> SUMMARY OF ASTM EB4 RESULTS: Because of the possible variations in reproducibility, the results are <br /> adjusted to the nearest figure divisible by 5. Smoke Density values over 200 are rounded to the nearest <br /> figure divisible by 50. <br /> In order to obtain the Flame Spread Classification, the above results should be compared to the following <br /> table: <br /> NEPA CLASS IBC CLASS FLAME SPREAD SMOKE DEVELOPED <br /> A A 0 through 25 Less than or equal to 450 <br /> B B 26 through 75 Less than or equal to 450 <br /> C C 76 through 200 Less than or equal to 450 <br /> BUILDING CODES CITED: <br /> 1. National Fire Protection Association, ANSI/NFPA No. 101, "Life Safety Code", 2006 Edition. <br /> 2. International Building Code, 2006 Edition, Chapter 8, Interior Finishes, Section 803. <br /> THIS REPORT IS THE CONFIDENTIAL PROPERTY OF THE CLIENT ADDRESSED.THE REPORT MAY ONLY BE REPRODUCED IN FULL.PUBLICATION OF EXTRACTS FROM THIS REPORT IS <br /> NOT PERMITTED WITHOUT WRITTEN APPROVAL FROM OAI.ANY LIABILITY ATTACHED THERETO IS LIMITED TO THE FEE CHARGED FOR THE INDIVIDUAL PROJECT FILE REFERENCED. <br /> THE RESULTS OF THIS REPORT PERTAIN ONLY TO THE SPECIFIC SAMPLE(S)EVALUATED. <br /> WWW.QAI.ORG <br /> info Ogai.org <br />