Laserfiche WebLink
� Input frequency: 50/60 hz <br /> Output Vo[tage: 3 phase, 0-480 Volts AC <br /> Frequency Rating: 100%continuous drive rating, Intermittent <br /> 1 t 1%Drive rating for one minute. <br /> _. Phase Failure and low voltage shutoff at 90%of motor name plate voltage on al[three legs 83%on one leg for five <br /> seconds. <br /> Low discharge pressure shutdown at 110 psi after a[I pumps are running for 60 seconds continuously. <br /> _ High discharge pressure shutdown at 130 psi after all pumps are running for 60 seconds continuously. <br /> Low water level safety shutdown if water falls to within two feet of pump sucteon. <br /> Relief Vatve Size: 4" <br /> Pressure Rating: 175 psi <br /> Pilot Setting: 160 psi <br /> Wye Strainer Size: 20" <br /> Pressure Rating: 200 psi <br /> Pressure Drop Through Clean Basket: 1.5 psi <br /> Flow sensor Brass, Pressure rating: 400 psi <br /> System Isolation Valve: 10" Pressure rating: 200 psi <br /> SKW Station Heater <br /> LS-32 2104GPM SS w/up to 30"adapter <br /> � <br />