Laserfiche WebLink
Automatic Vertical Turbine Variable Speed Prefabricated Pump Station Technical Specification <br /> Pumping System R4ode1 No. FPX- VWTP-1540-3-120 <br /> Total Design Criteria: Quantity of Pumps: 3 <br /> Total Design Flaw: 1500 GPM @ l20 psi <br /> Motor and Pump Data: PM Pump Pump#1 Pump#2 <br /> Motur Spec Motor h.p. 3 75 75 <br /> Motar rpna 3600 18Q0 I 800 <br /> Motor service factor 1.15 1.1� l.l 5 <br /> Motor efficiency 81% 91% 91% <br /> Motor power factor 88 87 g7 <br /> Motor type SUB 600 WP1 <br /> Motor disconnect volts 600 96 600 <br /> Motor FLA rating,amps 4.8 125 96 <br /> Motor fuse amps 6 125 125 <br /> Motor fuse AIC rating 2f1U,000 200,000 200,�00 <br /> Motor IEC starter size 9 1]0 110 <br /> Motor O.L. rating, amps 4.8 96 9f , <br /> Motor cfm requirements 48 ]200 1200 <br /> Tota! cfm requirements 2448 <br /> Pump Spec Pump gpm 25 750 750 <br /> Pump efficiency at design 65% $4.36% �436% <br /> Pump shut off head 450 420 420 <br /> Pump column pipe id 2" 6" 6" <br /> Pump shaft od n/a 2.25" 1.?5" <br /> Pump discharge size 2" 6" 6" <br /> Pump check valve size 2" � b" 6" <br /> Pump check rating, psi 200 200 200 <br /> Pump check psi drop at ca�acity .5 1.75 7.75 <br /> Pump discharge isalation valwe size 2' 6" 6" <br /> Pump disch. isolation valve rating, psi 20(} 200 200 <br /> Motor Starting Code G, Ctass F Insulation, <br /> Mrnimum water coverage as measured from eye of bottom impel(er: 24" <br /> Service Entrance; 206.$amps, 200,000 Fault Amps, i 62.9 KVA, 460 volts, 3 phase, b0 HZ <br /> Main Disconnect: b00 Valts, 400 amps <br /> Starting Equipment- U.L. Listed as Industrial Control Assembly: <br /> Controls U.L. Listed as Industrial Control Assembly. <br /> V1=D Controls U.L. Listed as Industrial Control Assemblv: <br /> Operating Temp: U to 40°C (32 - ]04 °F) <br /> Humidity: 5-95%Non-condensing <br /> Minimum Efficiency(full load, base speed)98% <br /> Input Voltage: 3 phase, 480 Valts AC <br />