� ' <br /> r <br /> ! <br /> Hennepin County Orono Maintenance Facility Expansion <br /> Plumbing <br /> Plan No.PLB1412-00075 <br /> Page 2 <br /> December 19,2014 <br /> 3. The combination fire protection/domestic water service shall comply with the backflow protection <br /> requirements of AWWA-M14, Chapter 6 (1990)with the exception that the following statement is deleted <br /> from section 6.3: "At any time where the fire sprinkler piping is not an acceptable potable water system <br /> material,there shall be a backflow-prevention assembly isolating the fire sprinkler system from the potable <br /> water system." <br /> Fire sprinkler systems in which corrosion inhibitors or other chemicals may be introduced either directly or <br /> by pumper connections require a reduced pressure zone(RPZ)backflow preventer on the public water <br /> supply. Local jurisdictions may require additional backflow protection. Please contact the local water <br /> purveyor for information concerning their requirements. <br /> 4. Pressure vacuum breakers must be installed at least 12 inches above spill line and no possibility of back <br /> pressure permitted. If a hose will be installed,the backflow preventer must be installed above the highest <br /> point that the hose will located when in use. The minimum recommended height is 6 feet 6 inches. <br /> 5. The plans indicate that a faucet with a hand-held sprayer will be provided. If it is possible to submerge the <br /> sprayer and contaminate the potable water system,then an approved backflow preventer shall be provided on <br /> the water supply to the sprayer(see Minnesota Rules,part 4715.2100). <br /> 6. The flammable waste interceptor installation shall comply with Minnesota Rules,part 4715.1120: <br /> a. The interceptor shall be located so it is readily accessible for service and maintenance. <br /> b. The interceptor may be constructed either: (i)of monolithic poured reinforced concrete with a minimum <br /> floor and wall thickness of six inches,(ii)of iron or steel of a minimum thickness of 3/16 inch,protected <br /> with an approved corrosion resistant coating on both the inside and the outside,or(iii)of fiberglass <br /> resins that comply with ASTM C581 and meet IAPMO Material and Property Standard,PS 80-2003b, <br /> for clarifiers. <br /> 7. Showers and combination showers-baths shall be equipped with individual thermostatic,pressure balancing, <br /> or combination thermostatic and pressure-balancing control valves in accordance with ASSE 1016(see <br /> Minnesota Rules,part 4715.1380, subpart 5). The maximum temperature setting must be set or adjusted in <br /> accordance with the standard and should not exceed 110 degrees F. <br /> 8. Equipment used for heating water or storing hot water shall be protected by approved safety devices in <br /> accordance with Minnesota Rules,part 4715.2210 and part 4715.2230. <br /> 9. In no case shall water from roofs be allowed to flow upon the public sidewalk(see Minnesota Rules, <br /> part 4715.2700). Verify that the discharge from all rainwater leaders will meet this requirement. <br /> 10. Sheet M1.1 shows 8-inch storm drainage pipe serving approximately 11,700 square feet of roof area exiting <br /> the building. A 8-inch horizontal storm drain can only accommodate 11,500 square feet of roof area at a 1/8 <br /> inch per foot slope(see Minnesota Rules,part 4715.2710,subpart 4).Verify that the referenced 8-inch <br /> horizontal storm drainage pipe is sloped'/a inch per foot slope at a minimum or else the pipe shall be <br /> increased to 10 inches in diameter. <br /> 11. All portions of the storm sewer system located within 10 feet of the building or water service line must be <br /> tested in accordance with Minnesota Rules,part 4715.2820. <br />