Laserfiche WebLink
� <br /> SECTION 16130 <br /> ' WIRE AND CABLE <br /> , 1.00 GENERAL <br /> A. All wire and cable shall be soft annealed 98% pure copper, #12 AWG minimum, <br /> ' 600 volt, type THWN-THHN. Wire size #14 AWG may be used for control <br /> wiring and where specifically called for or shown on the Drawings. Wire size #14 <br /> AWG through #10 AWG shall be solid; wire size #8 AWG and larger shall be <br /> ' stranded. Wire and cable color shall be in accordance with the latest edition of the <br /> NEC. On larger cables, where factory color coding is not available, marking tape <br /> shall be used to identify each phase and neutral conductors. A minimum length of <br /> , 6'° shall be color coded at each end. <br /> B. Aluminum wire shall not be used. <br /> ' C. The following manufacturers are approved for wire and cable: Anaconda, <br /> Continental Wire & Cable, Cyprus, General Electric, Houston, Pirelli, Rome, <br /> , Southwire and Triangle. <br /> ' D. The following manufacturers are approved for splices, termination lugs, etc.: <br /> Blackburn, Buchanan, Burndy, Ideal, Ilsco, T& B and 3M. <br /> ' END OF SECTION <br /> ' <br /> ' <br /> ' <br /> ' <br /> ' <br /> ' <br /> � <br /> � �21100 LGF102 3/14102 <br /> 16130 - 1 <br /> � <br />