Laserfiche WebLink
, fittings at all building expansion joints and as required by the NEC. Approval <br /> must be obtained from the Architect prior to any cutting of the building structure <br /> ' for raceway installation. <br /> T. Conduits shall be securely fastened with galvanized steel straps, clamps and <br /> ' hangers using appropriate anchoring systems. Straps, clamps and hangers shall be <br /> specifically designed for use with electrical conduit. <br /> � J. Conduits connected to equipment or lighting fixtures supported by or within a <br /> suspended ceiling may be supported from the suspended ceiling wires with <br /> "Caddy clip" type fasteners manufactured specifically for that purpose. No more <br /> ' than two 1/2" or one 3/4" conduit shall be supported from an individual wire. The <br /> number of conduits supported shall be the total of all installed conduits by all <br /> , trades, not just this Contractor. Tie wire shall not be used to support any conduit <br /> on the Project. All other conduit systems shall be supported from the building <br /> structure. <br /> ' ]�e The following manufacturers are approved for conduit: Allied, Carlon, Republic, <br /> Triangle, VAW of America , Youngstown, Sealtight and Alflex. <br /> ' L. The following manufacturers are approved for conduit fittings: Appleton, CH, <br /> Kellems, OZ Red Dot and T&B. <br /> ' <br /> END OF SECTION <br /> ' <br /> � <br /> ' <br /> , <br /> ' <br /> ' <br /> ' <br /> � <br /> , 020100 LGF102 3/14/02 <br /> 16110 - 2 <br /> , <br />