Laserfiche WebLink
Navarre Fire Station <br /> Plumbing <br /> Plan No. 033959 <br /> Page 2 <br /> June 26, 2003 <br /> 4. A full-size vent stack(3-inch minimum)must be provided for every building(see Minnesota Rules, <br /> part 4715.2520, subpart 1). This stack must be continuous in size from its base to its ternunal and should be <br /> the most remote stack from the location where the building drain leaves the building. The flammable waste <br /> interceptor vent does not meet this requirement due to the water seal in the interceptor. <br /> 5. The installation of reduced pressure zone bacl�low preventers is pernutted only when periodic testing is <br /> done by a trained backflow preventer tester acceptable to the administrative authority. Testing intervals <br /> shall not exceed one year, and records must be kept. All devices must be tested after initial installation to <br /> assure that debris from the piping iiistallatio�has not interfered with the functioning of the device. The <br /> devices shall be overhauled at least once every five years. The installation of new backflow preventers must <br /> be at least 12 inches,but not more than 6 feet above the finished floor or ground level. <br /> 6. Solvent weld joints in PVC and CPVC pipe must include use of a primer which is of contrasting color to the <br /> pipe and cement (see Minnesota Rules,part 4715.0810, subpart 2). <br /> 7. Type K copper pipe used for water service must be soft temper(see Minnesota Rules,parts 4715.0510,D). <br /> 8. The plumbing system shall be tested in accordance with Minnesota Rules,part 47152820. <br /> NOTE(S): <br /> l. The scope of this project consists of the construction of a new building. The plumbing installation includes <br /> restrooms, showers,counter sinks,and potable water connections to a pressure washer and truck fill <br /> equipment. <br /> 2. This facility is served by new municipal water and sewer service connections. <br /> Authorization for construction in accordance with the approved plans may be withdrawn if construction is not <br /> undertaken within a period of two years. The fact that the plans have been approved does not necessarily mean <br /> that recommendations or requirements for change will not be made at some later time when changed conditions, <br /> additional information, or advanced knowledge make improvements necessary. <br /> Approved: <br /> ��� <br /> Bradley . Erickson <br /> Public Health Engineer <br /> Environmental Health Section <br /> P.O. Box 64975 <br /> St. Paul,Minnesota 55164-0975 <br /> 651/215-0853 <br /> BCE:sas <br /> cc: Boarman Kroos Vogel Group, Inc. <br /> City of Orono <br /> Mr. Lyle Oman, Plumbing Inspector <br /> Plumbing Unit <br /> File <br />