FIRE PROTECTION SYSTEMS <br /> [F] 905.9 Valve supervision. Valves controlling water sup- dance with the provisions of this code and NFPA 72 shall be <br /> plies shall be supervised in the open position so that a change in provided in new buildings and structures in accordance with <br /> the normal position of the valve will generate a supervisory sig- Sections 907.2.1 through 907.2.23 and provide occupant noti- <br /> nal at the supervising station required by Section 903.4.Where fication in accordance with Section 907.9,unless other require- <br /> a fire alarm system is provided,a signal shall also be transmit- ments are provided by another section of this code. Where <br /> ted to the control unit. automatic sprinkler protection installed in accordance with <br /> Exceptions: Section 9033.L 1 ar 903.3.1.2 is provided and connected to the <br /> building fire alarm system, automatic heat detection required <br /> l. Valves to undergound key or hub valves in roadway by this section shall not be required. <br /> boxes provided by the municipality or public utiliry <br /> do not require supervision. The automatic fire detectors shall be smoke detectors. <br /> 2. Valves locked in the normal position and inspected as �ere ambient conditions prohibit installation of automatic <br /> provided in this code in buildings not equipped with a smoke detection, other automatic fire detection shall be <br /> fire alarm system. allowed. <br /> [F]905.10 During construction.Standpipe systems required �F]907.2.1 Group A.A manual fire alarm system shall be <br /> during construction and demolition operations shall be pro- installed in Group A occupancies having an occupant load I <br /> vided in accordance with Section 3311. of 300 or more.Portions of Group E occupancies occupied <br /> for assembly purposes shall be provided with a fire alarm <br /> system as required for the Group E occupancy. <br /> SECTION 906 Exception: Manua] fire alarm boxes are not required <br /> PORTABLE FIRE EXTINGUISHERS where the building is equipped throughout with an auto- <br /> [F] 906.1 General. Portable fire extinguishers shall be pro- matic sprinkler system and the alarm notification appli- <br /> vided in occupancies and locations as required by the Interna- ances will activate upon sprinkler water flow. <br /> tional Fire Code. <br /> [F] 907.2.1.1 System initiation in Group A occupan- <br /> cies with an occupant load of 1,000 or more. Activa- <br /> SECTION 907 tion of the fire alarm in Group A occupancies with an <br /> FIRE ALARM AND DETECTION SYSTEMS occupant load of 1,000 or more shall initiate a signal <br /> using an emergency voice/alarm communications sys- <br /> [F]907.1 GeneraL This section covers the application,instal- tem in accordance with NFPA 72. <br /> lation,performance and maintenance of fire alarm systems and <br /> their components. Exception: Where approved, the prerecorded <br /> F � announcement is allowed to be manually deacrivated <br /> [ ]907.1.1 Construction documents.Construction docu- for a period of time,not to exceed 3 minutes, for the <br /> ments for fire alarm systems shall be submitted for review sole purpose of allowing a live voice announcement <br /> and approval prior to system installarion.Construction doc- from an approved.constantly attended location. <br /> uments shall include,but not be limited to,all of the follow- <br /> ing: [F] 907.2.1.2 Emergency power. Emergency <br /> 1. A floor plan which indicates the use of all rooms. voice/alann communications systems shall be provided <br /> with an approved emergency power source. <br /> 2. Locations of alarm-initiating and notification appli- <br /> ances. [F]907.2.2 Group B.A manual fire alarm system shall be <br /> installed in Group B occupancies having an occupant load <br /> 3. Alarm control and trouble signaling equipment. of 500 or more persons or more than 100 persons above or <br /> 4. Annunciation. below Che lowest level of exit discharge. <br /> 5. Power connection. Exception: Manual fire alann boxes are not required <br /> 6. Battery calculations. where the building is equipped throughout with an auto- <br /> 7. Conductor type and sizes. matic sprinkler system and the alarm notification appli- <br /> ances will activate upon sprinkler water flow. <br /> 8. Voltage drop calculations. <br /> [F]907Z.3 Group E.A manua]fire alarm system shall be <br /> 9. Manufacturers,model numbers and listing infarma- installed in Group E occupancies. When automatic sprin- <br /> tion for equipment, devices and materials. kler systems or smoke detectors are installed,such systems <br /> 10. Details of ceiling height and construction. or detectors shall be connected to the building fire alarm <br /> 11. The interface of fire safety control functions. system. <br /> [F] 907.1.2 Equipment. Systems and their components Exceptions: <br /> shall be listed and approved for the purpose for which they 1. Group E occupancies with an occupantload of less <br /> are installed. than 50. <br /> [F]907.2 Where required.An approved manual,automatic or 2. Manual fire alarm boxes are not required in Group <br /> manual and automatic fire alann system installed in accor- E occupancies where a]] the following apply: <br /> 182 2006 INTERNATIONAL BUILDING CODE� <br /> _ <br />