<br /> CTTX OF'UZtOlY4—�'IRE A.�ARM Q�.
<br /> KITCHEN�X'l.'INGU�SHE�t/GEN�RAL PE�tMIT
<br /> (All pami4 must!x sPPmved by the I'irc FFia�'7h'N ar�dlor auilding OPl1�1�1)
<br /> i_ A,3i fire a(arm systems,vqMuntary or required try MinneSata State Building Code{MUBC)or
<br /> Mirtnesota State Fire Code(11�UFC)shal)be in�tatlod a»d m8dntained as per Nadonal Fire Pratectiori
<br /> Associatlon(NFPA)7z and 73�, 1996 editit�r►,National Elecytt'ical Code and manufacturers
<br /> requiremants.
<br /> 2. Part�oits ara tequired fot a!1 fire alarxr►system installtrtions. i�etxtlits can be obtainad from the City of
<br /> Oinono-Buildiz�g Offciat at,2750 Ke11y Parkway Orono,MN or via phone(952)249-4bQ0.
<br /> Patmits are alsa availabte anlino at:www ci.vr4na.mn.�s
<br /> 3_ Two sets of ptans an.d spacification sheets slaall ba submittect to the Orono Fire Marshal for approval
<br /> at least workin�ays before start of insta3�ation and shall in.clude:
<br /> a. 5peeiflcatiod data sheets�n a11 companents of system.
<br /> b, Ftoor placts ir►dicating locations of devices,fire alarm control p�nel�sub-pa»e15,transponders,
<br /> enunciatar,interconnecting wlring and zoning.
<br /> c, �'owar conqections inctuding source attd branch circuit data.
<br /> d. Type o�back up power system.
<br /> e_ Fise alarm control panel shall be compatible with all-devices.
<br /> f. All componet�ts of the system shal!be UL or k'M listed for their applications. Smoke
<br /> detectors shall be listed for commerCtal�ndustcial v�e•
<br /> 4. Ali systems shall be addressable.Smoke detectors shall be p�oto-electric_No eomb�nation
<br /> burg�ar/fire atarm systems are a)(owcd unless apptoved by tNke Orono Fira Marshai_
<br /> 5. Power supply for che system shall include battery back-u�with a UL tisted itre alarm panel_ Atarm
<br /> verification�s raquir�d�'or all systams using s;naoke detectora.
<br /> 6. The alanm system shal}be audible above the ambient noise ttve!in all areas of the building.
<br /> Audio/visual signalin�g devices ara required.
<br /> 7. When centXa!station notlftcation is required or ptovided it must be tfirough a iJI,or FM listed
<br /> catt�sunicatar or control panel_
<br /> 8. 1f a smoke detecting system installed in the tenant$pace of a buiiding is directly connected to the
<br /> building fire alarrn�pa�el,then
<br /> a. A zone on the alarm paneI must identt�the fenarit space or zone of the buitding ih�at the
<br /> system is locaied(i.o.,second floor,west wing).
<br /> b, A vist�J azv�unciation light sha!!be instailed on the cor►�idor side of the main door of the
<br /> teztants space and activate when the detection 5ystem in the tenants sgaoe activates.
<br /> 9. The system shalt be tested in thc presenco of the Orono Fire Marshal for final approvsl.
<br /> A�ipotntments can tse tnade by ca111ng the Fire Marshall at(952)d73-970i,
<br /> 24-h�urs notice is rec�acsted. The test will include:
<br /> a. Rar]dom testing of systam deviees.
<br /> b. Randorrt tesiing far system trouble and ground faed�tXouble.
<br /> c. Correct operation o£back-up power system.