<br /> RHVAC-Residential HVAC Load Calculations
<br /> Flare Heating&AIC Inc.
<br /> Elite Software Developrnent, nc. ,
<br /> Golden Valley, MN 55427-3700 _ _- -- -
<br /> , _ iI
<br /> System 9 Basement Summary Loads �
<br /> _._ _ _ . __
<br /> _ _ .
<br /> _ _ _ _Area Sen Lat S�n ' Total ;
<br /> Component
<br /> ' Description , Quan Loss Gain Gain Gain 1 '
<br /> . �..._
<br /> 4A Window Double Pane&Storm Clear Glass Wood Frame 213 6,682 0 4 858 4,858 �
<br /> 8M Glass Door pouble Clear Glass Wood Frame 100 5,069 0 1,600 1,600
<br /> 121 Wall R-19+ 1/2"Asphlt Board(R-1.3) 1564 7,914 0 2,030 2,Q30 �
<br /> 15C Wall 2-5' Below Grade 8/12" BIk+R-11 115 539 0 0 0
<br /> 15G Wali 5' or More Below Grade 8/12" BIk+R-11 1625 6,429 0 0 0 '
<br /> 21A Basemt Floor 2'or More Below Grade 3730 8,236 0 0 0
<br /> Subtotals for structure: 34,869 0 8,488 8,488 �
<br /> People: 4 920 1,200 2,120
<br /> Equipment: 0 0 0
<br /> Lighting: 0 0 0
<br /> Ductwork: 0 0 0 0 i
<br /> Infiltration: Winter CFM: 286, Summer CFM: 143 28,078 3,395 3,052 6,447 :
<br /> Ventilation: Winter CFM: 62, Summer CFM: 62 6,088 1,472 1,323 2,796
<br /> Sensible Gain Total: 14,063
<br /> Temperature Swing Multiplier: X 1.00
<br /> System 1 Basement Load Totals: 69,035 5,787 14,063 19,851
<br /> i
<br /> _, _ ___ .. _ _, . ,_ , _ , � .
<br /> ' Check Figures �
<br /> Supply CFM: 843 CFM Per Square ft.: 0.226
<br /> Square ft. of Room Area: 3,730 Square ft. Per Ton: 2,254.841
<br /> __. _, _ . ._ _ __
<br /> �System Loads '
<br /> Total Heating Required With Outside Air: 69,035 Btuh 69.035 MBH
<br /> Total Sensible Gain: 14,063 Btuh 71 % �
<br /> Total Latent Gain: 5,787 Btuh 29 %
<br /> Total Cooling Required With Outside Air: 19,851 Btuh 1.654 Tons (Based On Sensible+ Latent)
<br /> 1.929 Tons(Based On 75% Sensible Capacity)
<br /> _ _._
<br /> __. _ _. . ,._._ ,, __,
<br /> , .
<br /> j Notes _ , ,
<br /> Calculations are based on 7th edition of ACCA Manual J.
<br /> All computed results are estimates as building use and weather may vary.
<br /> Be sure to select a unit that meets both sensible and latent loads.