� �. <br /> W. W. GOETSCH ASSOCIATES, INC. <br /> � AURORA FIRE PUMP TEST <br /> DATE: APRIL 15, 1998 <br /> LOCATION MINNETONKA ENVIRONMENTAL SCHOOL, 2180 NORTHSHORE DRIVE, ORONO, MN <br /> CONTRACTOR OLSEN FIRE PROTECTION, INC., 321 WILSON STREET N.E., IVIINNEAPOLIS, MN <br /> AURORA PUMP MODEL 3-383-9A SN 97-66742 GPM 200 HEAD IN FEET 173 RPM 3500 <br /> MOTOR MFG U.S. ELECTRIC SN H13230/A10A2600054F HP 15 VOLTS 200 FLA 43 RPM 3480 <br /> CONTROLLER MFG FIRETROL FTA750 SN 170161 C TYPE LIMITED SERVICE <br /> CHECK BEFORE THE TEST DATE: 4/15/98 CHECK AFTER THE TEST DATE: 4/15/98 <br /> ALIGNMENT - FIRE PUMP CONTROLLER ON AUTOMATIC YES <br /> HOLD DOWN BOLTS X FIRE PUMP PRESSURE SWITCH SET PSI ON 65 RESET 75 <br /> LUBRICATION X JOCKEY PUMP CONTROLLER ON AUTOMATIC YES <br /> PRESSURE SENSING LINES X JOCKEY PUMP PRESSURE SWITCH SEI� PSI ON 80 OFF 90 <br /> CONTROLLER CONNECTIONS X CIRCULATION RELIEF VALVE SET - <br /> SIX (6) MANUAL STARTS X <br /> SIX (6) AUTOMATIC STARTS X <br /> ACCEPTANCE TEST DATE: 4/15/98 <br /> DISCHARGE SUCTION NET NET <br /> PRESSURE PRESSURE HEAD HEAD NOZZLE PITOT <br /> PSI PSI PSI FEET RPM VOLTAGE AMPERES SIZE PSI GPM <br /> 80 0 80 185 3557 210 23 23 24 - - 0 <br /> 74 -3 77 178 3496 209 39 38 41 1.75" 6 223 <br /> 71 -3 74 171 3479 208 40 4043 1.75" 8 257 <br /> 61 -3 64 148 3472 208 44 43 46 1.75" 12 308 <br />