REDUCED PRESSURE ZONE (RPZ) ASSEMBLY <br />TEST CERTIFICATION REPORT <br />THIS CERTIFICATION, issued on this 20th day of May, 2025, documents the inspection and testing of a <br />Reduced Pressure Zone Assembly. <br />1. TESTING INFORMATION <br />1.1 Certified Tester: Mark Manship ("Tester") <br />1.2 Testing Location: 1955 Heritage Drive, Orono, Minnesota 55391 ("Premises") <br />2. EQUIPMENT SPECIFICATIONS <br />2.1 Manufacturer: Wilkins/Zurn <br />2.2 Serial Number: ABN1414 <br />2.3 Model: As specified by manufacturer <br />3. TEST MEASUREMENTS AND RESULTS <br />3.1 Check Valve #1 Reading: 7.5 PSI <br />3.2 Check Valve #2 Reading: 7.5 PSI <br />3.3 Relief Valve Differential: 2.3 PSI <br />4. CERTIFICATION <br />Based on the above measurements and in accordance with applicable standards, this RPZ Assembly has been <br />determined to PASS all required testing criteria. <br />CERTIFIED BY: <br />Mark Manship <br />Certified RPZ Tester <br />Date: May 20, 2025 <br />