HomeMy WebLinkAbout2018-00295 - mechanical "'4 RECEIVED Cot (C
•
FOR CITY USE ONLY
42750
City of Orono MAR AA ���p C.1r F%tl',sti
P.O.Box 66 D�te" e Pem»t#
Kelley Parkway Cor / GCrystal Bay,MN 55323 $v� Amount$:
Phone(952)249-4600 Fax(952)249-4N( VVtf CITY OF ORONO-MECHANICAL PERMIT
(All Commercial permits must be approved by the Building Official or Inspector and/or Fire Marshall)
GENERAL INFORMATION 2,4 0;1 L
1. You may apply for mechanical permits by mail or in person at the City offices. Applications will
be reviewed and a permit will be issued within two working days.
2. Permit cards will be sent by return mail after a review is completed. PERMITS ARE NOT
VALID UNTIL YOU RECEIVE A PERMIT. WORK MUST NOT BEGIN UNTIL THE
PERMIT CARD IS POSTED ON THE JOB SITE.
3. Mechanical Designs—Complete calculations,details and specifications are required for each
heating,ventilation,humidification-dehumidification,and air conditioning installation including
heat less/heat gain calculation,design temperatures,equipment ratings and identification as to
type,manufacturer and model. Data shall be presented on form provided.
4. When any new construction or remodeling is involved,a separate building permit must be
obtained.
5. All work must be done in accordance with the Uniform Mechanical Code/State Building Code I c i.I
requirements.
6. All work must be inspected(rough-in and final). Call(952)249-4600. —�
(24-48 hour notice required)
7. House Heating Test Record must be submitted before final.
TYPE OF PERMIT
(Check All That Apply)
[residential ❑Commercial(Approval Required) [Backflow Device: ❑AVB ❑PVB]
❑New ❑Additional ❑Repairs \R-Replace
'o
ao
Job Site/Owner Information:
4.4
AU
Site Address: J LiU i''‘' f h t-
Owner: J.e P/ C ac I co h Mailing Address: Skv-N
City: 0 r n u Zip: 5-'3/1
Home Phone: 0 2. - 9 ..f —4 9'r f Alternate Phone:
Contractor Information:
r Total Comfort Contact Person: rh , I f j r r
4A\ 9.- 4,.....4 5
` _ _ 8818 7th Ave N n
TQ TAL / a Golden Valley, State Bond#: 3
Gom 7 MN 55427
/Jill. Expiration Date: 9 /30 il r
.1 -
Phone: 3 I f Alternate Phone:
J Insurance-Current: In
01.P164''
_ p� GMrU/-- 1 (i lis1/V
OA..$ -3/ //.6 3 / ii
1. CONTRACT PRICE *is 1.25%of contract price with a(Minimum Fee of$50.00)
)00 x.0125$ 2 . 1-0
(contract price) (minimum$50.00)
2. STATE SURCHARGE
0°C' x.0005 $ 2.1 ft/
(contract price)
3. POSTAGE&HANDLING(Only on Mail-In Applications) $ 2.00
4. TOTAL PERMIT FEE(Add Lines 1-3 Above)
■ * CONTRACT PRICE or JOB COST means the actual or estimated dollar amount charged for the
permitted work including materials,labor,profit,and other fixed costs. It is the amount to be charged
to the customer for the work done. If any material,equipment,labor or installations are furnished by the
owner, tenant or any other party, the reasonable market value of such items must be added to the
estimated cost or contract price for permit fee purposes. In the event that there is a dispute on the amount
of the job cost, the City may request the submission of a signed copy of the actual contract.
The undersigned hereby applies to the City for issuance of a Mechanical Permit, agrees to do all
work in strict accordance with the ordinances of the City and the regulations of the State of
Minnesota,and certifies that all statements made on this application are complete,true and correct.
Applicant's Signature: rC6a0EL- Date: 7 P
3
Note:All Geothermal Systems will now require a Site Plan&Review by our Building Official.
IS THIS GEOTHERMAL? 0 Yes ❑No
HEATING SYSTEMS
Quantity: /
Make: Cgfrter
Model:
Fuel: /Jc )* rtJ G c S
Flue Size:
Input BTUs:
Output BTUs:
CFM:
COOLING SYSTEMS
Quantity: 1
Make: Cn Irr I C l
Model:
Tons:
H.Power
FIREPLACES
❑ Gas Factory Fireplace Brand Name:
❑ Wood Burning Fireplace
❑ Wood Stove Model No.:
❑ Wood Stove with Flue/Masonry
VENTILATION
❑ No. Kitchen Exhaust duct recirculating cfm
❑ No. Bath Exhaust(must have duct outside) cfm
❑ No. Other Fans: Locations cfm
FUEL STORAGE (Must be approved by Fire Marshall ifproposing to abandon tank in place.)
❑ Installation 0 Removal
Fuel Oil: gallons 0 Underground 0 Inside 0 Outside
LP Gas: gallons
Other:
GAS LINE ONLY
❑ Outdoor Grill 0 Other/List What&Where:
2
I 1
DatL: Mar 09, 2018
RECEIVED
MAR 1 4 2018
CITY OF ORONO
Contractor Information
Company Name Total Comfort
Street Address 8818 7th Ave , Golden Valley, MN 55427
Name: Heat Load
Phone 763-383-8383
Email heat_load@tcomfort.com
Customer Information
Street Address 3747 Livingston ave, Wayzata, MN 55391
Latitude, Longitude 44.9793°, -93.273°
House Square Footage: 1508 sq. ft.
Name: Jeff CarlsonFull Name
Phone: 123-123-1234
Email: example@mail.com
Design Conditions
Outdoor Heating Cooling
Dry bulb (°F) -15 92
Daily range M
Relative humidity 50%
Moisture difference 25
Indoor Heating Cooling
Indoor temperature (°F) 70 74
Design temperature difference(°F) 85 18
House Information
SHR .75
Number of residents 2
Ceiling height 9
Wall U-value I R-value 0.09 111
Floor U-value I R-value 0.2 I 5
Ceiling U-value I R-value 0.053 119
Window U-value 0.5
Window SHGF 0.85
Moisture grains 25
Duct loss % 0
Duct gain % 0
Cooling infiltraction (ACH) 0.6
Heating infiltration (ACH) 0.8
Winter ventilation 0
Summer ventilation 0
Heating Loads
Area Btuh % of load
Wall 8617 15.9
Floor 15390 28.4
Ceiling 6474 11 .9
Windows 8748 16.1
Infiltration 14995 27.7
System Efficiency Loss 0 0
Total: 54223
Heating Loads
54,223 BTU hr
r System Efficiency Loss
Ceiling
Floor -N
Wall
Windows
Infiltration
Adequate Exposure Diversity
AED Graph
15000
10000
ca
5000
0
8am 9am 10am 11am 12pm 1pm 2pm 3pm 4pm 5pm 6pm 7pm 8pm
— Hourly Loads —Average
Equipment selection
System equipment selection will be made using the following derived values.
Glass (E) 109 sq. ft.
Glass (S) 15 sq. ft.
Glass (N) 15 sq. ft.
Glass (W) 77 sq. ft.
Summer Outdoor 92°F
Summer Wet Bulb °F
Summer Indoor 74°F
Summer Design Grains 50%
Winter Outdoor -15°F
Winter Indoor 70°F
Sensible Cooling 22,678 Btuh
Latent Cooling 2,606 Btuh
Required Cooling Airflow 1,031 CFM
Sensible Heating 56,901 Btuh
Required Heating Airflow 739 CFM
SOFTWARE VALIDATION:All calculations are based upon approved HVAC industry standards and procedures,ACCA Manual J 8th Edition
calculations,retrieved weather data based on NOAH locations nearest the home being investigated.The code uses BIN data and not heating or
cooling degree day methods.The house image is pulled from Google Earth and the real estate data is pulled from Zillow(when available).
All calculations comply with all local,state and federal code requirements and meet or exceed the requirements of the 2012 International Energy
Conservation Code(IECC)paragraph 403.6 in their entirety as verified by independent engineer William M.McMahon Jr. P.E.CEM.The
programs are properly based on standard engineering heat loss/heat gain formulas coupled with the appropriate weather data,location factors,
general home construction materials,user designated for energy unit costs,and other considerations normally used in the HVAC industry.It is
my professional opinion,that the program,while consistent with calculations in ACCA Manual J,can be considered as meeting the"other
approved heating and cooling calculation methodologies"and do not require approval from ACCA.
Further.Paul Welch.P.E.;FL Reg.No.29945 affirmed that the software computes building heating and cooling loads and sizes equipment in a
manner consistent with good engineering practice and approved heating and cooling load calculations methodologies and fully complies with
Florida Building Code and Energy Conservation Codes.All computed results are estimates. Product developed and maintained by Energy Design
Systems. Inc.
" 1
DATE TIME
CITY OF ORONO CALLED IN
INSPECTION OTK,ESCHEDULED c." Y/ /''' /�:e
PERMIT NO. V1 O 2 ' COMPL ED
ADDRESS 7 7 G VLi/i 6)4AI-
owNER
�'._ . I_/ ./A ELEPHON O.1O/I-70-4 95
r
N7R
CO . • 111 .f4 .
il—
DESCRIPTION ,' G
W ❑ FOOTING 0 DEMO-FINAL 0 SEPTIC FINAL
Q ❑ POURED WALL 0 PLUMBING RI 0 EXCAV/GRADING/FILLING
CO
❑ FOUNDATION DRAIN TILE 0 PLUMBING FINAL El TREE REMOVAL
❑ LATHE ❑ MECHANICAL RI 0 SITE INSPECTION
Q 0 FRAMING 0 MECHANICAL FINAL 0 RATED WALLS
• ❑ INSULATION 0 WOOD BURNER/FIREPLACE 0 COMPLAINT
!:t 0 FINAL 0 WATER HOOK-UP 0 FOLLOW-UP
W ❑ AS BUILT-SURVEY ❑ SEWER HOOK-UP 0 FOUNDATION/REMOVAL
v ❑ -SITE 0 SEPTIC INSTALL
'7( OWNER/C NTRACTOR TO MEET YOU:_g YES_NO
2 COMMENTS: 0rep 1a6...ew►u-6-
Q. ' /cCC
k€,S Gap5 ®rvL.;raP�
o 1L f ro 6ve-:.:iic).! A,),(4-, Ori /p e Saxe
k prov ivea
0
w a 5e4/ /f^a se a,p
e et t.--464z).--
cc
• .40 41ro1'( 7 G/e1 i rrc¢Z /ay•C=1- aC40G
P rt ilei cl.sca n P..
W
IQ
1;i'lal�
W 0 WORK SATISFACTORY:PROCEED PROJECT COMPLETE
W ECT WORK&PROCEED 0 ISSUE CERTIFICATE OF OCCUPANCY
O 0 CORRECT WORK,CALL FOR REINSPECTION TEMPORARY
✓ BEFORE COVERING PERMANENT
❑CORRECT UNSAFE CONDITION WITHIN HOURS. ❑ PHOTO TAKEN
INSPECTOR WILL RETURN
CISTOP ORDER POSTED.CALL INSPECTOR ❑CITATION ISSUED
❑INSPECTION REQUIRED.CALL TO ARRANGE ACCESS.
Call for the next inspection 24 hours in advance. (952) 249-4600
Owner/Contractor on site:
Inspector. ' L/11"-
White Copy/Inspector's File Canary Copy/Site Notice