fire alarm info
I 1-22-97 Plan Review Notes (Fire Alarm System) Address, 1025 Old Crystal Bay Road North Owner; Orono Hockey Association Inspector; Lyle Oman Building Official Proposed work; Ice Arena Fire alarm system Occupancy classification; A2.1 Requirements -Uniform Building Code Section 303.9 "An approved fire alarm system shall be installed as set forth in the Fire code in Group A, Divisions 1, 2 and 2.1 occupancies." -Uniform Fire Code Section 14.104(b) 1. "General. Group A , Division 1, 2 and 2.1 Occupancies shall be provided with a manual fire alarm system." 2. "System initiation. Activation of the manual fire alarm shall immediately initiate an approved prerecorded message announcement using an approved electrically supervised voice communication or public address system which is audible above the ambient noise level of the occupancy." 3. Emergency power. "Voice communication and public address systems shall be provided with an approved emergency power source." -Uniform Building Code section 1105.4.6 " Alarms.Alarm systems,when provided,shall include both audible and visible alarms. The alarm devices shall be located in hotel guest rooms as required by Section 1103.1.2.9.3;accessible public-and common-use areas, including toilet rooms and bathing facilities; hallways; and lobbies". F4 H GENERAL NOTES ELECTRICAL SYMBOLS NOMINAL MOUNTING A. MOUNT EQUIPMENT AT NOMINAL MOUNTING HEIGHT INDICATED IN ELECTRICAL SYMBOL SYMBOL DESCRIPTI❑N HEIGHT SCHEDULE UNLESS NOTED OTHERWISE ON THE FLOOR PLANS OR DETAILED IN LIGHTING AND POWER ARCHITECTURAL ELEVATIONS. DIMENSION SHOWN IS TO CENTER LINE OF BOX, ® LIGHT FIXTURE ** B. SEE ARCHITECTURAL INTERI❑R ELEVATIONS FOR EXACT LOCATION OF WALL MOUNTED C_� LIGHT FIXTURE ** DEVICES AND LIGHT FIXTURES. ® EXIT LIGHT ** C. INSTALL INSULATED GREEN GROUND CONDUCTOR WITH ALL BRANCH CIRCUIT AND 0 LIGHT FIXTURE ON ** FEEDER CONDUCTORS, SIZED PER NEC 250-95, EMERGENCY CIRCUIT PART OF LIGHT FIXTURE D. SEE ARCHITECTURAL REFLECTED CEILING PLANS FOR FINAL L❑CATION OF CEILING ❑N EMERGENCY CIRCUIT MOUNTED EQUIPMENT. ()9- LIGHT TRACK ** E. THREE AND FOUR LAMP FLUORESCENT LUMINAIRES ARE TO BE BI-LEVEL SWITCHED '-� POLE MOUNTED LIGHT ** WITH OUTBOARD LAMPS CONNECTED TO SWITCH %' AND INBOARD LAMPS CONNECTED FIXTURE TO SWITCH 'b', TYPICAL UNLESS NOTED OTHERWISE. 419- SINGLE POLE SWITCH 48' F. IN GENERAL„ BRANCH CIRCUIT CONDUIT AND WIRE IS NOT SHOWN. PROVIDE CONDUIT -692 2 POLE SWITCH 48' AND WIRE TO CONNECT DEVICES TO CIRCUITS SHOWN, WIRE FILL AND CONDUCTOR 4,43 3 WAY SWITCH 48' SIZE SHALL BE AS SPECIFIED. -644 4 WAY SWITCH 48' -69K KEY OPERATED SWITCH 48' _164M OD MOMENTARY CONTACT SWITCH DIMMER/DIMMER CONTROL 48' 48' DRAWING INDEX E001 ELECTRICAL SYMBOLS, SITE PLAN -64P SWITCH WITH PILOT LIGH148' � SEPERATE PILOT LIGHT a8• E201 LIGHTING FLOOR PLAN Q OCCUPANCY SENSOR ** E301 POWER AND SIGNAL FLOOR PLAN QT TIME CONTROL ** E401 SCHEDULES ONE LINE DIAGRAM © PHOT❑CONTROL ** -e SINGLE 125V RECEPTACLEI8' =0 DUPLEX 125V RECEPTACLEI8' -9 SPECIAL PURPOSE ** RECEPTACLE DOUBLE DUPLEX 18' RECEPTACLE EMERGENCY DUPLEX 18' RECEPTACLE < EMERGENCY DOUBLE 18' DUPLEX RECEPTACLE SWITCHED OR SPLIT 18' WIRED RECEPTACLE JUNCTION BOX -- Q FLOOR BOX -- © CLOCK 80' PUSHBUTTON 48' MUSHROOM TYPE 48' PUSHBUTTON —Pl— SURFACE MOUNTED RACEWAY ** —Rl— UNDERFLOOR RACEWAY -- SYSTEM SYMBOL EXPLANATION COMMUNICATION ® VOICE\DATA OUTLET 18' ® PAY TELEPHONE 48' DEVICES SHOWN IN THIS MANNER INDICATE THE GANGING P 49 OR b9 TOGETHER OF THE DEVICES UNDER COMMON COVER PLATE. INTERCOM 18' UPPER CASE LETTER INDICATES LIGHT FIXTURE TYPE. LOWER CASE a COMPUTER SYSTEM 18' boA 23 INDICATES CONTROL, NUMBER INDICATES CIRCUIT CONNECTION. OUTLET (SEE LIGHT FIXTURE SCHEDULE) aTVwinTELEVISION OUTLET * ARROWS CONNECTED TO A DEVICE INDICATE AIMING DIRECTION. ARROWS AUDI❑ NEAR ALL EXIT SIGNS IDENTIFY DIRECTION OF ARROW ON FACE PLATE. _- SHADED PDRTWN OF EXIT SIGN INDICATES FACE(S) TO BE ILLUMINATED, SPEAKER VOLUME CONTROL 48' �D SPECIAL RECEPTACLES. THE TYPE IS SHOWN WITH LETTER, SEE THE SPECIAL RECEPTACLE SCHEDULE AN UPPER CASE FOR THE ® MICROPHONE OUTLET 18' DESCRIPTION. AUXILLARY OUTLET 18' �2 THE CIRCUIT DESIGNATION IS SHOWN BY NUMBER FOR ADJACENT EQUIPMENT. PROJECTOR CONTROL 18' EXAMPLEi DUPLEX OUTLET ON CIRCUIT NUMBER 2. OUTLET "D600 WALL BOX DIMMER WITH SIZE AS INDICATED AT DEVICE. EXAMPLE] POWER DISTRIBUTION 600 WATT WALL BOX DIMMER. /Cy MOTOR -- THE SYMBOL INDICATES TYPE OF DEVICE TO BE INSTALLED IN THE SAFETY DISCONNECT ** FLOOR BOX, EXAMPLE, A FLOOR BOX WITH A DUPLEX RECEPTACLE SWITCH AND A TELEPHONE OUTLET. ® MAGNETIC STARTER ** SYMBOL WITH EQUIPMENT IDENTIFICATION. SEE MOTOR OR COMBINATION STARTER ** ,�EF-1 EQUIPMENT SCHEDULE FOR COMPLETE ELECTRICAL INFORMATION. MANUAL MOTOR STARTER ** EXAMPLEt EXHAUST FAN #1. ® RELAY OR CONTACTOR A UPPER CASE LETTER INDICATES SPEAKER TYPE. ® CONTROL STATION -- SEE SPECIFICATIONS. ® TRANSFORMER -- -� LIGHT FIXTURES OR DEVICES SHOWN WITH STEM ARE TO BE WALL MOUNTED o POWER OR DISTRIBUTI❑N ** PANEL PLAN KEYED NOTE. SEE KEYED NOTE SCHEDULE ON THAT SHEET. ARROW PANELBOARD ** 1 POINTS TO THE ITEM TO WHICH THE NOTE APPLIES. SECURITY ® CODE CARD READER 40' 3/4'C #8 INDIVIDUAL HOME RUN TO BRANCH CIRCUIT PANELBOARD. PANELBOARD ANDMO MONIT❑RING DEVICE ** ` CIRCUIT DESIGNATION ARE PLACED ADJACENT TO HOMERUN ARROW, MULTI-POLE L Q DOOR LOCK/STRIKE 77- L2A CIRCUIT BREAKERS ARE INDICATED BY THE FIRST POLE NUMBER FOLLOWED BY CAMPS / NUMBER OF POLES). EXAMPLE] HOMERUN TO PANEL L2A. oa TELEVISION CAMERA ** L315 UNDESIGNATED SLASH MARKS INDICATE #12 C❑NDUCTORSI NO SLASH MARKS OUTLET INDICATE 2 #12 CONDUCTORS. CONDUCTOR SIZES INDICATED ADJACENT TO SLASH MARKS SHALL APPLY TO ENTIRE CIRCUITS. FIRE ALARM ® SMOKE DETECTOR -- -P1— 'Pl' OR 'Rl' INDICATES RACEWAY TYPE, REFER TO SPECIFICATIONS DUCT SMOKE DETECTOR -- OR o—Rl— ® SPRINKLER FLOW SWITCH -- ® GATE VALVE SWITCH -- r--{� 'm' or 's' INSIDE LIGHT FIXTURE INDICATES FIXTURE IS PART OF ® MAGNETIC DOOR HOLDER J MASTER/SATELLITE COMBINATION. DASHED LINE INDICATES FACTORY ® DAMPER OPERATOR INTERCONNECT. ® FIRE ALARM MANUAL 48' STATION ® FIRE ALARM AUDIO- 80' VISUAL UNIT ELECTRICAL ABBREVIATI❑NS ® FYRE ALARM VISUAL UNIT 80' �{ FIRE ALARM CHIME 80• LFjQ FIRE ALARM AUDIO UNIT 80' ABBREV. DESCRIPTION [ FIRE FIGHTER PHONE JAC148' A,AMP AMPERE MCC MOTOR CONTROL CENTER ® HEAT DETECTOR -' A/C AIR CONDITIONING MIN MINIMUM HEAT DETECTOR HIGH -- AFF ABOVE FINISH FLOOR MISC MISCELLANEOUS TEMPERATURE AIC AMPERE INTERRUPTING MLO MAIN LUGS ONLY AL CAPACITY MHS ALUMINUM MOA MANUAL MOTOR STARTER MULTI-OUTLET ASSEMBLY CONDUIT AND WIRING APPROX APPROXIMATELY MTR MOTOR CONDUIT CONCEALED IN -- ARCH ARCHITECT, ARCHITECTURAL WALL OR OVERHEAD ATS AUX A�JTOMATIC TRANSFER SWITCH N/C A X1UlA1ty NEC NORMALLY CLOSED NAiIUNAL ELLL;IKICAL LUTA_ /V iDivLuii iurvEtALEy iri -- AV AUDIO VISUAL NEMA NATI❑NAL ELECTRICAL OR BELOW FLOOR CTURER'S CONDUIT INSTALLED -- BLDG BUILDING ASS❑CIA I® EXPOSED NFSS NON-FUSED SAFETY C CONDUIT SWITCH —• CONDUIT VERTICAL -- CB CIRCUIT BREAKER NIC NOT IN CONTRACT TRANSITION CCTV CLOSED CIRCUIT TELEVISION N/O NORMALLY OPEN CLG CEILING NTS NOT T❑ SCALE �-y CONDUIT STUBBED OUT -- CONN CONNECTION CONDUIT SEAL -- CONT CONTINUOUS OR OL CONTINUATION OVERLOADS /\ EXISTING-C❑NDUIT -- CRT CATHODE-RAY TUBE P POLE/ EX EXISTING CONDUIT -- C/T CURRENT TRANSFORMER PA PUBLIC ADDRESS INTERCEPTED CEN CENTER PE PNEUMATIC ELECTRIC CU COPPER PF POWER FACTOR , UTA UNDERGROUND TELEPHONE -- DISC PH DISCONNECT PNL PHASE PANEL / L----, LOW VOLTAGE CABLE -- DIST DISTRIBUTION PP POWER POLE 1--k. INDIVIDUAL BRANCH -- DN DOWN PR PAIR' CIRCUIT HOMERUN DWG DRAWING PRI PRIMARY PROD PROJECTION MISCELLANEOUS ECB ENCLOSED CIRCUIT BREAKER PRV P/T POWER ROOF VENTLATOR PO T E:11ITIAL TRANSFORMER BUZZER vv' ELL ELEC ELECTRIC(AL) ,_ _ECTRIC( ':= r; ; ? 1 PT e moi; ,,. P^i I JTNYL CH�CRIL i EP �I Et.ECTf''IC PiJEUNATIC READ REQi ED i LA GtiiHc 30' EQUIP EQUIPMENT BELL BO° EWC ELECT RTC WATER COOLER SJQ SOLID EXST EXH EXISTING EXHAUST SPECIFICATION ,�;, CROSS HATCHING OF DASHED SYMBOL -- EXP SPEC EXPLOSION PROOF SPKR SPEAKER F "< INDICATES REMOVED F FUSE SP STD SPARE STANDARD DASHED SYMBOL -- FA FIRE ALARM SW SWITCH INDICATES EXISTING FLR FLOOR SWBD SWITCHBOARD EQUIPMENT AS NOTED ** SWGR SWITCHGEAR GALV GALVANIZED SYM SYMMETRICAL GFI GROUND FAULT CIRCUIT SYS SYSTEM KEYED NOTE '- GNP INTERRUPTER TEL GROUND TELEPHONE GYP GYPSUM TERM TERMINAL XFMR TRANSFORMER HOA HAND-OFF-AUTOMATIC SWITCH TV TELEVISION H❑RIZ HORIZONTAL TYP TYPICAL HP HGT HORSEPOWER HEIGHT UE UNDERGROUND ELECTRICAL HV HIGH VOLTAGE UG UNDERGROUNDUH UNIT HEATER - JB JUNCTION BOX UT UNDERGROUND TELEPHONE KV KILOVOLT V VOLT KVA KILOVOLT-AMPERE VA VOLT AMPERES KVAR KILOVOLT-AMPERE REACTIVE VDT VIDE❑ DISPLAY TERMINAL KW KILOWATT VERT VERTICAL KWH KILOWATT HOUR VFD VARIABLE FREQUENCY DRIVE VOL VOLUME LV LOW VOLTAGE W WATT ** - SEE DRAWING SPECIFICATION OR LIGHTING W/ W/O WITH WITHOUT FIXTURE SCHEDULE FOR MOUNTING HEIGHT WP WEATHERPROOF F4 H