HomeMy WebLinkAbout2006-P09758 - alarm system PERMIT
CITY OF ORONO
Permit Number:
2750 Kelley Parkway- PO Box 66 P09758
Crystal Bay, Minnesota 55323 Permit Type: Fire Systems Permit
(952) 249-4600 Date Issued:
4/21/2006
SITE ADDRESS: 770 Old Crystal Bay Rd N Unit#
Long Lake,MN 55356
PID: 28-118-23-43-0005
DESCRIPTION:
Proposed Use: Institutional-Schools
Permit Class: General
Permit Type: Fire Systems Permit Permit Sub-type(s): Alarm System
YP
DETAILS:
Approved per resolution#:
Separate permits required:
NOTICES/REMARKS:
To Be Inspected By Fire Marshal-Bill Meyer 612-490-2307
FEE SUMMARY: Permit Fee: $ 35.00 Valuation: $ 2,432.00
State Surcharge Fee: $ 1.22
TOTAL FEE: $ 36.22
APPLICANT: Sonitrol OWNER: Independent School Dist#278 (Orono)
1230 Eagan Industrial Rd#140 38 ADDRESS UNASSIGNED
Eagan,MN 55121 MN 00000
THE UNDERSIGNED HEREBY REQUESTS PERMISSION TO MAKE THE REAL IMPROVEMENTS SPECIFIED
AND AGREES TO DO ALL WORK IN STRICT COMPLIANCE WITH ALL CITY OF ORONO ORDINANCES AND STATE OF
MINNESOTA BUILDING CODE REQUIREMENTS.
411,Z1 1
APPLICANT PERMITEE SIGNATURE ISSUED BY SIGNATURE
Copies: 1-File(Signatures Required), 1-Applicant, 1-Monthly Reports, 1-Assessing,(If Septic, 1-Septic) Page I
. 't • ' 4,p� Cit of Orono ^wp�
Y C> FO��CITY�7SE ONLY
0 Co P.O.Box 66 1140(P Date Received: �f•1 q•D(p Perm 975g,
2750 Kelley Parkway r
d Crystal Bay,MN 55323 Amount: S
4exoe4 (952)249-4600 �p
Approved By: ry�4,4,44f. ❑Charge Plan Review
Recommends: Approval it Denial ❑
CITY OF ORONO—FIRE ALARM OR
KITCHEN EXTINGUISHER/GENERAL PERMIT
(All permits must be approved by the Fire Marshall and/or Building Official)
1. All fire alarm systems,voluntary or required by Minnesota State Building Code(MUBC)or
Minnesota State Fire Code(MUFC)shall be installed and maintained as per National Fire Protection
Association(NFPA) 72 and 72E, 1996 edition,National Electrical Code and manufacturers
requirements.
2. Permits are required for all fire alarm system installations. Permits can be obtained from the
Orono Fire Marshal(952)473-0234 or Orono Building Official at,2750 Kelly Parkway Orono,MN,
phone(952)249-4600. Permits are also available online at:www.ci.orono.mn.us
3. Two sets of plans and specification sheets shall be submitted to the Orono Fire Marshal for approval
at Icast7 N\orking_dm s before start of installation and shall include:
a. Specification data sheets on all components of system.
b. Floor plans indicating locations of devices,fire alarm control panel, sub-panels,transponders,
enunciator,interconnecting wiring and zoning.
c. Power connections including source and branch circuit data.
d. Type of back up power system.
e. Fire alarm control panel shall be compatible with all devices.
f All components of the system shall be UL or FM listed for their applications. Smoke
detectors shall be listed for commercial/industrial use.
4. All systems shall be addressable. Smoke detectors shall be photo-electric.No combination
burglar/fire alarm systems are allowed unless approved by the Orono Fire Marshal.
5. Power supply for the system shall include battery back-up with a UL listed fire alarm panel. Alarm
verification is required for all systems using smoke detectors.
6. The alarm system shall be audible above the ambient noise level in all areas of the building.
Audio/visual signaling devices are required.
7. When central station notification is required or provided it must be through a UL or FM listed
communicator or control panel.
8. If a smoke detecting system installed in the tenant space of a building is directly connected to the
building fire alarm panel,then
a. A zone on the alarm panel must identify the tenant space or zone of the building that the
system is located(i.e.,second floor,west wing).
b. A visual annunciation light shall be installed on the corridor side of the main door of the
tenants space and activate when the detection system in the tenants space activates.
9. The system shall be tested in the presence of the Orono Fire Marshal for final approval. The test will
include:
a. Random testing of system devices.
b. Random testing for system trouble and ground fault trouble.
c. Correct operation of back-up power system.
6/1/2004
• 40 775S?
` •
FIRE ALARM OR KITCHEN EXTINQUISHER PERMITS 4///i/o
Please Check One:
(l New ❑ Addition ❑ Remodel Replace
Job Site/Owner Information:
770 Old CrystaIl Bay Road North Long Lake,MN 55356
Site Address:
Orono Student Center 770 Old Crystal Bay Road North
Owner: Mailing Address:
Orono 55356
City: Zip:
(952)449-8314 Alternate Phone: (612)919-1769
Home Phone:
Contractor/Applicant Information:
Don King
Contractor/App.: Sonitrol Contact Person:
1230 Eagan Industrial Rd. Suite 140 TS00827
Address: State License#:
Eagan 55121 07/31/06
City: Zip: Expiration Date:
Phone: (651)755-0693 (651)452-0223
Alternate Phone:
TYPES OF FIRE PERMITS
✓❑ Commercial—Fire Alarm ❑ Commercial—Fire Extinguisher
Fire Systems Permit Fire Systems Permit
* (Per UBC) *k(Per UBC)
Contract Price:$v( 7 Contract Price: $
❑ Residential—Fire Alarm
Fire Systems Permit
(Per UBC)
• Contract Price: $
*Note: Permits are calculated with UBC Fee Schedule;submit application and we will call you with a total fee for the
permit
I herby apply for a Fire Alarm/Extinguisher Permit and I acknowledge that the information above is complete
and accurate; that the work will be in conformance with the Ordinances and Codes required by Minnesota
State Building Code(MUBC)or Minnesota State Fire Code(MUFC)shall be installed and maintained as per
National Fire Protection Association (NFPA) 72 and 72E, 1996 edition, National Electrical Code and
manufacturers requirements;that I understand this is not a permit and work is not to start without a permit;
and that the work will be in ccordance with the approved plan.
yr /'7 7&
Applicant Date
Reset Form