HomeMy WebLinkAbout2017-01589 - new septic CITY OF ORONO II 111111 H I I II
* 2 0 1 7 - 0 1 5 8 9
2750 KELLEY PARKWAY DATE ISSUED: 12/05/2017
ORONO,MN 55356-
(952)249-4600 FAX: (952) 249-4616
ADDRESS : 1840 FOX ST
PIN : 03-117-23-42-0008
LEGAL DESC : HI ACRES TWO
: LOT 001 BLOCK 001
PERMIT TYPE : SEPTIC
PROPERTY TYPE : RESIDENTIAL
CONSTRUCTION TYPE : SEPTIC(NEW OR REPLACEMENT)
ACTIVITY : SEPTIC(MOUND)
NOTE: SIZE OF TANKS-2250 AND 1300
PRECST CONCRETE
MOUND SYSTEM
APPLICANT SEPTIC NEW OR REPLACEMENT 400.00
BURSCH BROTHERS INC. TOTAL 400.00
Payment(s)
P.O.BOX 55 CHECK 4092 400.00
HANOVER,MN 55341
(612)221-1493
Minnesota State License#:BUIL-2727
OWNER
MCNAE,ANGILEA
1840 FOX ST
WAYZATA,MN 55391-
AGREEMENT AND SWORN STATEMENT
The work for which this permit is issued shall be performed according to
the approved plans and specifications,applicable City approvals,and the
State Building Code. This permit is for only the work described and does
not grant permission for additional or related work which requires separate
permits. All provisions of laws and ordinances governing this type of work
shall be compied with whether or not specified herein.This permit will
expire and become null and void if construction authorized is not
commenced within 180 days of the date of issuance,or if construction is
suspended for a period of 180 days at any time after work has commenced.
The applicant is responsible for assuring all required inspections are
requested in conformance with the State Building Code.This permit may be
revoked at any time for due cause.
6--77 q61 5
Applicant Permitee Signature Date Issued By Si ure 1)atc
City of Orono FOR CITY USE ONLY
114 - PP.O.Box66
2750 Kelley Parkway Date Received: 4/3-5--/7
r Crystal Bay,MN 55323 Permit# � li 7 / CP?
Phone:(952)249-4600
44 HOPE Fax: (952)249-4616 Approved By:
Amount S.
CITY OF ORONO —SEPTIC SYSTEM PERMIT APPLICATION
(All permits must be approved by the On-Site Septic Manager and/or Building Official)
Site Address: 1t 4E St
Owner: }4p Q-i. [ ( . , Mailing Address: k S'S 144-bJ--- ttit,,
City: �- -- /,1.-J Zip: 2-:-
Home
,Home Phone: 4012- 2:7 i_ 1c/'0 Alternate Phone: t '/2..Z2 1- Ne
S.4s T?_ - ,vo f trA
Contractor/A
PP: ����x-� g�'�s • . Contact Person:
Address: ?c. ��,� S'� State License #: L 2424
City: 1-17-1,,0.12r- J14J Zip: s`S 34' / Expiration Date: Z t)C
Phone: ri a -22 I- 1-1 Alternate Phone: 442 -ZZ/_ /'/`33
f Residential ❑ Commercial ❑ Other
El.7
.lc ,., � f � � ..w`' k.s.. ..t � ... � 4
Tanks:
Ng Precast Concrete ❑ Fiberglass ❑ Plastic
❑ Other:
Number of Tanks: Z
Size of Tanks: 22.5t h444.0, /3tb
Type of Activity:
❑ Trenches Mound ❑ Pressure Bed ❑ Chambers ❑ Holding Tanks
❑ Pre-Treatment ❑ Other
NOTE: Provide an As-Built of the system before the final inspection.
A 24-HOUR NOTICE IS REQUIRED FOR ALL INSPECTIONS.
Page 1
^t .-poem'.$. E�w.*"tT7�< f..« '* <,�.� �, . isl:..L3t3G.tt v ,rs:',lu
Ne r Replacement System $400.00
Repair Existing System 100.00
(Tanks or Drainfield)
Total $
The undersigned hereby applies to the City of Orono for issuance of a septic system
installation permit, agrees to do all the work in strict accordance with ordinances of the City
and regulations of the State of Minnesota and certifies that all statements made on this
application are complete, true and correct.
Signature of Applicant .- - Date: t Z-
MPCA License No.: Z4 2-4
Staff Review: cept Ti Denied
Date: /Z/51`7
Reviewer:
Reason for Denial:
Comments (to be printed on inspection card):
1. Applications for septic system permits may be mailed or submitted in person at the City
offices; however, permits will not be mailed out. The permit must be picked up in person at
the City offices and work must not begin unless the permit card is on the job site.
*** DO NOT MAIL PAYMENT WITH THIS APPLICATION ***
2. Permits will be only issued to contractors holding a Minnesota Pollution Control Agency
(MPCA) Septic System Installers License.
3. All work must be done in accordance with the approved septic system design.
4. The following inspections will be required for all septic systems:
A. Tank installation prior to covering.
B. Drainfield trench installation prior to covering. For mounds, inspection is required after
rough up, but prior to sand placement (sand must be jar tested for silt content) and
again during pressure distribution piping installation in the rock bed.
C. Final inspection to verify final cover depths and to verify that all pump station (where
required) components are functional and comply with codes.
5. MPCA licensed Installers or their DRP (Designated Responsible Person) shall be present
during all inspections.
Page 2
THIS SYSTEMBEDROOMSIS DESIGNFO
•
' /0 X 51) j(04. ,� . ANY INCREASEEDR
IN NUMBER
OF BEDROOMS INVALIDATES THIS DESIGN.
/- /30.0
Z° P9/1 Joseph Olson D.B.A.
y- 7z Rusty Olson's--Soil and Percolation Testing
Joseph J. Olson--MPCA License#810
11481 Riverview Rd. NE, Hanover, MN 55341
(763)498-8779 Fax (763)498-8290 ',
rorm
Revised April 18,2017
Hendel Homes
1840 Fox Street
Orono. Hennepin County
This on-site Sewage Treatment System is designed for a Type 1 four-bedroom home in
accordance with the Minnesota Pollution Control Agency Chapter 7080 and local ordinances. The
future site is a type ltl. Drainage will need to be rerouted if it is used.
The periodically saturated soils were located at 26-30 inches(mottled soil). Due to the
periodically saturated soils,a pressurized mound system with 6 inches of rock will need to be
installed to treat the septic effluent. The bottom of the treatment area must be located at least 3'
above the saturated soils.This system is designed with 6 inches of rock
All neighboring wells are greater than 100' from proposed treatment areas.
The soils at a depth of 12"have a percolation rate averaging 5 MPI.
A 2250 combination septic tank needs to be installed.
All new tanks need to be insulated if there is less than two feet of cover over the top of the tanks,
Clean outs must be installed on the end of the laterals for maintenance.
A 1300 gallon pumping chamber will need to be installed to lift the effluent to the treatment area.
The power supply and switches must be located outside the,manhole and pumping chamber in a
weatherproofenclosute. Ayvarning device must„be installed with light and sound devices;this is
in case of a pump failure. A ftow^measurementtle\•itemu'st be installed. Including but not limited
to a water meter"event counter,running.titne clocks_or.electronically controlled dosing.
Nothing other than grin'water; .14004ower ,etch,)Huinan water and toilet tissue
should be disposed of into the septic tanks.Garbage disposals are not recommended.
Additives must not be used: they may cause harmful damaie to your septic system. It is
recommended that You Dump the tank every year for 1 septic tank,every two years for two
septic tanks.
Sincerely. ,
CITY OF ORONO
SEPTIC PE IT PL.e4EVIEW
INSPECTOR
Joseph J. Olson DATE /2, / ERMIT NO. 7A/7-0158
0 APPROVED AS SUBMITTED
HAPPROVED WITH CORRECTIONS AS NOTED
n NOT APPROVED-CORRECT& RESUBMIT
Tht>sc comments are for your information. All work shall he done
in full compliance with all applicable septic and tonin!code.
Requirements including items:nnt,nccilieally noted in this review.
KELP THIS PLAN SET f U\ Ni I.Al ALl 1IMI.S
•
g• ? w-
•,,
./..•
,••• .....,0%
• ..-.11 t."\:.,
.44
•
.
...
-ra yt 7-Ly ,c .:_t,w jj cf,,0. :Cc,,,,>V) Lt-t.)- ,•'1.C (jolt Z....mft•4": • .1.
4,.
ScALZ.: I -
''.1.•5o
olar
• •t•".'t •
.
....•
ou 10..2
ri.)102.4 .
.41
,
m .3.
•
''..
VI
,:/..,/ ;i1,1 ‘• 44
i --. ....•
.\ •
i.• < •
• •
„.-- \•.! , .t. ' •,s
CO.
otd 0/ • ' '. . •
•
sv.• , is s.,
4:\ •
/
•
'4. / ., \•,, A. .:6,. . , •,,
•\, 0 5. : "X • s•Iiiel isi‘
As -*• 1
;.
lAr
nvcA • / / "."'' 0
s.•,:- • . •/
r e•
,..0.............."/".."1/
."-------------....2\ .,.„ •-•
.......„...-41. , ,e ,...
te4
\ /
ND
\ / -
4 .."-..''.-. ...)
°2..•
.....___. -
......--
------ - ...
A,
..• -
-).'4.!',..., •
, -,.... w,.. .,
...• 4.--t..• *"
- , •:,,•:;',... 4;4‘ 1 s. .74,0%,.....",
,... si•4*, \e,s;•4111‘ X',..
.' ,,`,:•., ,-"• ,t..
•••• •
S. .; ,,,, *01,
• s„.
N....5
2 gm,
,0 i.l't
,
__•
••••, 1/.7.0.4...'
.101. •-••-•,_ ,ekit,,,, ..,*•
- •,,„'
0
",r* , -,-...................
..,..***-
....reire4,44 ''"—. - 5L; >.::::- .7--- ,-. 7
.•
....4 s
43
/! ,.:*04* --................ ‘. %
mu bo •L
......")
N...) ••%rr'6,' :, .• -------...,--"---',,
t , .
C• 4 .
. '
/1/,.,,, 11,0.-•:Iteeks, , 4.4.1
rt •
7 0 \
• f:'‘
ik ...„,..,_
0*,:,:i.V
4\ \ ' ...'- `"''----."-...._ I i-74,,I•F`Z. A,
,
. \1.,* 4,...E.
PROPOSED .14-------______
.... E.
i- 44--,...
mOUSE
•- •;:-.r..!
4
•1840
...-- !.
. ., - . •
Ti "
ve,
1 . - -
„+• "...
.
6'.:7--... w
Id.”
-I 1 c L......21
'
i*Paksib
do
-A A.m. -----" ...*.-4' 7 , ""•••••••.............
----ft.__ .'•\ in
Ca
• \
----
,-. ..
II
L 107,rAT,,,,A, '• II 1
t \ nii• St
...• 1 . .." "4' /--1-10:.----
,.-
lot
Q
a
9 .01.. I.
o ,..--• e
NJ 1110•,
, , .iiiit:„ . ,.• -, „a. ii•••
. 1
..,.
!.>
„: • .,,,
n Oe
....
..
•••:'.. .;. .....,AIM N
......
....
....
MI ....
.
-
--
S ao.saor w .... — -212.90 .
- ni.„ -,- .ger. ----c---- last 4.
11 es.'t r r4rry-i 7-1 1-1 rrl tr.,.
'n L' ` Iv n s'.
n` 1.
a b n
L_ .� W a 5 C CL' '-i: •• i w
'try A CA
_~ ..
1- 1 ETHifi 9 ..c 'G1".pZ w °
e ,--' I2 y0�. ._ it "" c ! ii
Or i
i M $ k D i /Jr
/
§ 14 1 1, , g. ) 8 as EF.
n
tL` . Y
I l&t, 1 E 1, ? :7, II F2 , t : ,+ I
/
Q ra -IZ citiO 'I * i i i• ‘,..1 I
.�\/ , � ! {
(); by G w G C p� :ti + r `
i� ro' P s • i i s f1 UN0. '
Z I ii pi iii! .ii
[ I ''':. 1 2 oT
i
i ".4'3 44 z q i c)
3 ow'
�F i p 7
t. R♦
' '''Vi . . .
1.4. . I° _Eigifi
:?.:A. ( I;
,_ r (4.0 . 117 El ir ,.. 4:1-CTr:),::)
:, it e; k . 19
la SI
.;j .
Pi.; LIW„IN. 1! p"` ,� •
1 et 1 /........t.:y
.1/ /
r. r It all 0 .
cl, 1 /
•
i1 -- Li,/i / .
1 I .1 tlil bbi43 = 0
r" , rr , 4r/ .
I * -,-f)
t rw �)'�p "tie j �(
1,2
n" is"'i \ii {71 ' t / r 1 1
V, Z I Lle
1
2011 purple code Mound Design
www.SepticResource.com (vers 15 2)
Property Owner: Hendet Homes Date: 4/18/2017
Site Address: 1840 Fox Street PID: 0311723420008
Comments:
instructions: -enter data =adjust if desired 1, = computer calculated- DO NOT CHANGE!
4 bedroom Type I Residential System
600 GPD design flow
Yes Garbage disposal or pumped to septic 50%larger tank with multiple comp/tanks
4, 2250 Gal Septic tank(code minimum) 2250 Gal Septic tank(design size / LUG req'd)
Tank options: none
1.2 GPD/ft2 mound sand loading rate contour loading rate of 12 req's a min 50 ft. long rockbed
10.0 ft rockbed width , 50.0 ft rockbed length
3.0 ft lateral spacing 3.0 ft perforation spacing (maximum of 3 for both)
end feed manifold connection
S, 3 laterals 48.0 feet long 17.0 perfs / lateral 51 perfs total
(1/2 a perf means the first perf starts at the middle feed manifold)
7/32 inch perfs at 1 feet residual head gives 0.56 gpm flow rate per perforation
for this perf size&spacing, &pipe size on line 12, max perfs/lateral= 30 , line#8 must be less-->
i(, 4.0 doses per day ( 4 minimum)
150 gallons per dose (treatment volume)
2.00 5x
2.00 inch diameter laterals must be used to meet"4x pipe volume"requirement
2.00 3x
122 feet of 2.0 inch supply line leads to 21 gallons of drainback volume
(Tip: "top feed"manifold to control the drainback)
14' 171 gallons TOTAL pump out volume (treatment+drainback)
16 feet vertical lift from pump to mound laterals, leads to a:
16, 29 GPM® 25 ;feet of head, Pump requirement (note: >50gpm may require an extra 3-6'of head)
17: 500 gal Dose tank (code minimum) 1300 gal Dose tank(design size / LUG req'd) at 25.49 gpi
leads to a
!ro 6.7 inch swing on Demand float, or timed dosing of 5.9 min ON (confirm pump rate with drawdown
(this delivers Average flow, =70%of Peak design flow) 9 hrs OFF test and adjust as necessary)
12 inches from bottom of tank to"Pump OFF"float
19 inches from bottom of tank to"Pump ON"float, or 12 � inches to"Timer ON"float if time dosed
22 inches from bottom of tank to"Hi Levet"float, or 32 inches to"Hi Level"float if time dosed
22 739 gallons reserve capacity (after High Level Alarm is activated)
0.60 gpd/ft2 Absorption area Soil Loading Rate, which gives a mound ratio of 2 (minimum)
(this must match the soil boring log) desired mound ratio 2.0
24 Fr—percent site slope (0.20% range) 8 (%downslope site slope, if different than upslope)
25, 26 inches, or 2.2 ft. to Redox or other limiting condition (need at least 12"to be a Type I)
Treatment zone contains 0 inches of 0%soil credit, and 0 inches of 50%soil credit. Giving a:
12 inch, or 1.0 ft. Sand Lift Mound CRITICAL FOR FUTURE CERTIFICATIONS!!!
:7; 20.0 ft.Total ABSORPTION width (with sand beyond rockbed as follows:)
28; 0.0 ft. upslope and sideslope
10.0 tft. Downslope
Individual slope ratios give BERM widths (topsoil beyond rockbed)of:
2a, 4:1 upstope ratio 10 ft. upslope berm
;, , 3:1 sidestope 12 ft. sideslope berms
3f 4:1 downslope 20 ft. downslope berm
?=) Overall Dimensions: 10.0 ft. wide by 50.0 ft. long Rock bed
40 ft. wide by 74 ft. long Mound footprint
4" inspection pipe
18" cover on top
{Upstope berm t0 a '< Downslope berm 20
� � 12" cover on sides
• (6"loamy cap&6"topsoil)
1.0
Clean sand Cif'
2.2
Absorption Width [ 20.0
Note:
For 0 to 1% slopes. Absorption Width is measured from the Bedequally in both directions.
For slopes 51%, Absorption Width is measured downhill from the upslope edge of the Bed.
33, Rock Bed:
10.0 ft. by 50.0 ft. by 6 inches under pipe, plus 20%gives 17 yd'or*1.4= 24 ton
34, Mound Sand: (note: volume is based on 3:1/4:1 slope from top of rockbed, Exchange sand for loamy cap if desired)
14.8 up + 56.3 downslope + 8.7 ends+ 25.9 under rock= 127 yd'or"1.4= 178 ton
plus 20%
;c Loamy Cap:
36 ft. by 70 ft. 6"deep, plus 20%gives 56 yd'or*1.4= 78 ton
3b. Topsoil:
40 ft. by 74 ft. 6"deep, plus 20%gives 66 yd'or 1.4= 92 ton
I hereby certify that I have completed this work in accordance with all applicable ordinances, rules and laws.
Rusty olson's Soil& Perc 810 4/18/2017
igner Signature Company License# Date
Installer Summary
2250 gallon Septic tank (minimum) Tank options: none
U b wiser Lana wun rnutupie comp/t.an$S
1300 gallon Dose tank (minimum) at 25.49 gpi
29 GPM 0 25 ft. of head, Pump required
6.7 inch swing on Demand float which translates to roughly 4.4 inches of float tether length
if time dosing is required --> 5.9 minutes ON time Ft 9 hours OFF time
19 inches from bottom of tank to"pump ON"float, or 12 inches to"timer ON"float
22 inches from bottom of tank to"Hi Level Alarm"or 32 inches to"Hi level alarm"if time dosed
122 ft. of 2.0 ,inch supply line with end feed manifold connection
(Tip: "top feed"manifold to control drainback)
12 inch, or 1.0 ft. Sand Lift Mound
10.0 ft. wide by 50.0 ft. long Rock bed
3 laterals 2.00 inch diameter 48.0 ft. long 3.0 ft. lateral spacing
7/32 inch perfs 3.0 ft. perforation spacing
No Effluent filter&alarm
3 clean out&varve box assemblies
20.0 ft.Total sand ABSORPTION width (minimum)
0.0 ft. upslope and sideslope (sand beyond rockbed, minimum)
10.0 ft. Downslope
Specific slope ratios give BERM widths (topsoil beyond rockbed)of:
4:1 upslope ratio 10 ft. upslope berm
3:1 sideslope 12 ft. sideslope berms
4:1 downslope 20 ft. downslope berm
4' inspection pipe
18" cover on top
Upslope berm 10 Downslo•e berm 20
001
annum- 12" cover on sides
r _._` �____ ________ _ (6"loamy cap&6"topsoil)
1.0 iE'ziti SGtiCi flit "�•�.`^
2.2
Absorption Width 20.0
Note: II"
For 0 to 1%slopes, Absorption Width is measured from the Bedequally in both directions.
For slopes >1%. Absorption Width is measured downhill from the upslope edge of the Bed.
Rock Bed: 17.0 yd3 or*1.4= 24 ton 6 inches under pipe
Mound Sana: 127 yd3 or"1.4= 178 ton calculation based on 3:1/4:1 slope from top of rockbei
Loamy Cap: 56 yd3 or"1.4= 78 ton 6"deep
Topsoil: 66 lyd3 or*1.4= 92 ton 6"deep
INSPECTOR CHECKLIST - mound
1641U Iox street
EiWELL setbacks: 20'to pressure tested sewer line (5 psi for 15 min)
-1 50'to everything 100'to dispersal area with shallow well
f PROPERTY LINES setback: 10'to everything
-1 Road setback: platted: 10'prop line. Metes ft bounds: out of road easement, or outer ditch.
LAKE BEI"FT setback: 20'for bluff, Lakes: GD , RD_, NE . Protected Protected wetland_.
Building setbacks: 10'for everything, 20'for dispersal area.
.d WA FER LINE under pressure sl 10'to bed,tank Et sewer line. (else sewer line > 12"below)
E] Sewer line Et baffle connection (no 90's, 3'between 45's, slope min 1"in 8', max 2"in 8')
(no depth req's, clean out every 100', Sch 40 pipe)
ESeptic tank and risers (water tight, insulated, proper depth, existing verified by pumping)
mfg 2250 gallons none
Riser over outlet, riser over inlet or center, and 6"+inspection pipe over any remaining baffles.
No effluent fitter&alarm
—
Dose tank risers and piping (water tight, insulated, proper depth, drainback)
—
mfg 1300 gallons
L_ dose pump 29 gpm 25 head VERIFY PUMP CURVE 5.9 min ON 9 hr OFF
El float setting drop 6.7 inches at 25.5 gpi "DESIGNED" 4,4 inches approx float tether length
171.0 gal dose divided by gpi "INSTALLED" = inches float drop(field corrected
LABEL pump requirements and drawdown on riser or panel
Cam lock reachable from grade- 30"max. J-hook weep hole. Supply line access (no hard 90's)
2.0 inch supply pipe: Sch40, sloped 1/8"+, supported by 4"sch40 sleeve or compacted, and buried 6"+.
splice box / control panel /electrical connections
flow measurement: CT, ETM, time dosed, home water meter
mound absorption area rough up
mound rock dimensions 10.0 X 50.0
Sand lift depth 12 inches. (Jar test: 2"sand leaves < 1/8"silt after 30 min)
ElAbsorption Sand beyond rock 0.0 upstope 10.0 downslope
Bermed topsoil beyond rockbed 10 upslope 12 sideslope 20 downslope
cover depth of 12-18"+ VERIFY
3 laterals (1-2'from edge of rock)
2.00 inch pipe size (Sch40 pipe a fittings)
3.0 ft lateral spacing
7 7/32 inch perforations
3.0 ft perforation spacing
Air inlet at end of laterals, and at top feed manifold if necessary. VERIFY
clean outs (no hard 90's)
4"inspection pipe to bottom of rock, anchored VERIFY
(— Abandon existingsystem -if necessary y Re•use existing tank certification
monitoring plan and type
well abandonment form - if necessary
System Elevations 44
y...4 A.444 wu a v N..u a.
benchmark
_ - - - SHWT
Mound 1
(Grade elevations are existing. If a _ loamy cap
different final grade is desired it should
lateral
be shown and described here.)
bottom rock
grade (al up4Mpe iot k bed)
SHIRT (at upstope roc k bed)
a:..1.'jMAleaaa vM.1awty M�..�IA���A.A.•JgV,ipm,~woaa AvANdvh.+,SI dalaAaalv.+1drawee 44,4, Awix.S,.*Ma
-11
1 1 1 I
lrt.
Sewer pipe
exiting house Septic Tank Septic Tank (a apt&able) Pump Tank
Grade Grade Grade Grade
Pipe inlet inlet inlet
Tank bottom Tank bottom Tank bottom
•
Logs of Soil Borings
License#810
Location or Project: 1840 Fox Street
Borings made by: Rusty Olson's Soil and Perc Testing Date:8/18109
Classification System: AASHO ; USDS-USDS-SCS X ; Unified ; Other
Auger used (check two): Hand X_, or Power , Bucket or Probe_X_, Pit
Boring Number_1_Surface elevation 73.8 3-1,1. Mottled Soil at_2.5_feet
0"-6" Dark brown loam to sandy loam 10yr3/2 H2O present at X_feet
6"-24" Brown loam to sandy loam 10yr4/4
24"-30" Brown loam to sandy loam 10yr5/4
30"-36" Rusty brown loam 10y6/4
Boring Number_2_Surface elevation 79-:8 Mottled Soil at_2.1_feet
0-12" Dark brown loam to sandy loam 10yr3/2 H2O present at_X_
12"-26" Brown loam to sandy loam 10yr4/4
26"-32" Rusty brown loam to sandy loam 10yr4/4
Boring Number_3_Surface elevation_87:1 Mottled Soil at_2.1_feet
0-6" Dark brown loam 10yr3/2 H2O present at_X_
6"-14" Brown loam 10yr4/4
14"-26" Brown loam 10yr5/4
26"-32" Rusty brown loam 10yr5/3
Boring Number_4_ Surface elevation_87':9_ Mottled Soil at2.3feet
0"-6" Dark brown loam to sandy loam 10yr3/2 H2O present at X_
6"-18" Brown loam to sandy loam 10yr4/4
18"-28" Brown loam to sandy loam 10yr5/4
28"-36" Rusty brown loam to sandy loam 10y5/4
Boring Number_5_Surface elevation v Mottled Soil at_2.1_feet
0-12" Dark brown loam to sandy loam 10yr3/2 H2O present at_X_
12"-26" Brown loam to sandy loam 10yr4/4
26"-32" Rusty brown loam to sandy loam 10yr4/4
Boring Number_6_Surface elevation 86..4 Mottled Soil at_2.3_feet
0-18" Dark brown loam to sandy loam 10yr3/2 H2O present at X_
18"-28" Brown loam to sandy loam 10yr4/4
28"-36" Rusty brown clay loam 10yr5/4
Percolation Test Data Sheet
Lic.#810
Percolation test readings made by: Rusty Olson's Perc. starting at 8:49 A.M. On 8/19/09
Location: 1840 Fox Street
Hole number: 1
Date hole was prepared:8/18/09
Depth of hole bottom_12"_inches, Diameter of hole_6"_inches.
Soil data from test hole:
Depth, inches Soil texture
0-6" Dark brown loam to sandy loam 10yr3/2
6"-12" Brown loam to sandy loam 10yr4/4
Method of scratching side wall: Knife
Depth of gravel in bottom of hole 2 inches:
Date and hour of initial water filling 8/18/09 At 11:00 A.M. depth of initial water filling 12 inches
above hole bottom.
Method used to maintain at least 12 inches of water depth in hole for at least 4 hours Automatic Siphon
Maximum water depth above hole bottom during tests 6 inches
I Time Time Depth Drop in H2O Perc Rate
8:59 9:14 6" 3.5 4.3
9:21 9:36 6" 3.3 4.5
9:37 9:52 6" 3.3 4.5
AVERAGE PERC. RATE 4.4 MPI 1
Percolation Test Data Sheet
Lic.#810
Percolation test readings made by: Rusty Olson's Perc. starting at 8:49 A.M. On 8/19/09
Location: 1840 Fox Street
Hole number: 2
Date hole was prepared:8/18/09
Depth of hole bottom_12"_inches, Diameter of hole 6" inches.
Soil data from test hole:
Depth, inches Soil texture
0-12" Dark brown loam to sandy loam 10yr312
Method of scratching side wall: Knife
Depth of gravel in bottom of hole 2 inches:
Date and hour of initial water filling 8/18/09 At 11:00 A.M. depth of initial water filling 12 inches
above hole bottom.
Method used to maintain at least 12 inches of water depth in hole for at least 4 hours Automatic Siphon
Maximum water depth above hole bottom during tests 6 inches
Time Time Depth Drop in H2O Perc Rate
9:00 9:15 6" 3.8 3.9
9:20 9:35 6" 3.7 4.0
9:38 9:53 6" 3.7 4.0
AVERAGE PERC. RATE 4.0 MPI
Percolation Test Data Sheet
Lic.#810
Percolation test readings made by: Rusty Olson's Perc. starting at 8:49 A.M. On 8/19/09
Location: 1840 Fox Street
Hole number: 3
Date hole was prepared:8/18/09
Depth of hole bottom__12"_inches, Diameter of hole_6"_inches.
Soil data from test hole:
Depth, inches Soil texture
0-6" Dark brown loam 10yr312
6"-12" Brown loam 10yr414
Method of scratching side wall: Knife
Depth of gravel in bottom of hole 2 inches:
Date and hour of initial water filling 8/18/09 At 11:00 A.M. depth of initial water filling 12 inches
above hole bottom.
Method used to maintain at least 12 inches of water depth in hole for at least 4 hours Automatic Siphon
Maximum water depth above hole bottom during tests 6 inches
Time Time Depth Drop in H2O Perc Rate
9:01 9:16 6" 3.0 5.0
9:19 9:34 6" 2.8 5.3
9:39 9:54 6" 2.7 5.6
AVERAGE PERC. RATE 5.3 MPI
Percolation Test Data Sheet
Lic.#810
Percolation test readings made by: Rusty Olson's Perc. starting at 8:49 A.M. On 8/19/09
Location: 1840 Fox Street
Hole number: 4
Date hole was prepared:8/18/09
Depth of hole bottom_12"_inches, Diameter of hole_6"_inches.
Soil data from test hole:
Depth, inches Soil texture
0-6" Dark brown loam to sandy loam 10yr312
6"-12" Brown loam to sandy loam 10yr4/4
Method of scratching side wall: Knife
Depth of gravel in bottom of hole 2 inches:
Date and hour of initial water filling 8/18109 At 11:E1./ . depth of initial water filling 12 inches
above hole bottom.
Method used to maintain at least 12 inches of water depth in hole for at least 4 hours Automatic Siphon
Maximum water depth above hole bottom during tests 6 inches
I Time Time Depth Drop in H2O Perc Rate
9:02 9:17 6" 3.6 4.2
9:18 9:33 6" 3.5 4.3
9:40 9:55 6" 3.5 4.3
AVERAGE PERC. RATE 4.3 MPI
‘21----12-t-----
DATE`') TIME
CITY OF ORONO CALLED IN /z-L4 /
INSPECTION N TICE SCHEDULED /5-7-i7 Mei
PERMIT NO. 7 4:15 co ED
ADDRESS
OWNER - TELEPHONE NO.07 -Z21-X43
CONTRACTOR a CA `� 5 191 4
-6.10/7c.....)
DESCRIPTION
ty ❑ FOOTING 0 DEMO-FINAL 0 SEPTIC FINAL
11.
❑ POURED WALL 0 PLUMBING RI 0 EXCAV/GRADING/FILLING
Q ❑ FOUNDATION DRAIN TILE 0 PLUMBING FINAL 0 TREE REMOVAL
❑ LATHE 0 MECHANICAL RI 0 SITE INSPECTION
cr ❑ FRAMING 0 MECHANICAL FINAL 0 RATED WALLS
F=. ❑ INSULATION 0 WOOD BURNER/FIREPLACE 0 COMPLAINT
Q 0 FINAL 0 WATER HOOK-UP 0 FOLLOW-UP
11J___
❑ AS BUILT-SURVEY 0 SEWER HOOK-UP 0 FOUNDATION/REMOVAL
v ❑ DEMO-SITE 0 SEPTIC INSTALL
2 OWNER/CONTRACTOR TO MEET YOU:_YES_NO
to• COMMENTS:
cc
W
a
j ,. :i `, ,,,,..,,,-
0
I/
0O /
edW
ix
Q
W
z
W
it
O• .
W 1ScWORKSATISFACTORY:PROCEED U PROJECT COMPLETE
�u!1 0 CORRECT WORK&PROCEED U ISSUE CERTIFICATE OF OCCUPANCY
O U CORRECT WORK,CALL FOR REINSPECTION TEMPORARY
✓ BEFORE COVERING PERMANENT
O CORRECT UNSAFE CONDITION WITHIN HOURS. U PHOTO TAKEN
INSPECTOR WILL RETURN ❑CITATION ISSUED
❑STOP ORDER POSTED.CALL INSPECTOR
U INSPECTION REQUIRED.CALL TO ARRANGE ACCESS.
Call for the next inspection 24 hours in advance. (952) 249-4600
Owner/Contra n site: _�
Inspector.,` ' �__ ,_;, J/..C-
v` t
White Copyllnspector's File Canary Copy/Site Notice