from: Lyle Oman,
Date: December 8, 1997
Pages: One
Van,
The city has no problem with a temporary ramp that meets
code requirements. Please send over a drawing for review.
The basement stairs however is a different matter. A stair
way as part of a required exit must meet code before
occupancy. If there was a way to meet cod� with a
temporary stair the city could allow it. Tenting the area of
the stairs is not as difficult as protecting the flat work area
and should be easily accomplished this year. If you have
any more questions feel free to call me.
From the desk of...
Lyle Oman,
Building Official
City of Orono
P.O. Box 66
Crytal Bay Mn.
473-7357
Fax: 473-05 I 0
Memo to: Van Erickson
Re: Handicap Ramp 2180 North Shore Dr.
From: Lyle Oman Building Official
Date: 8-17-98
I have reviewed code requirements for the above mentioned ramp and find the following;
1- No handrail or guardrail is required by the state building code. However I would
recommend keeping one for safety purposes.
2-42' deep frost footing are required.
3- Ramp must meet the requirements of Uniform Building Code table 16A, uniform
concentrated load of 1001bs. per sq. ft.
4- Ramp must be accessible from the handicap parking stall.
5-Ramp must have a non slip surface.
The Orono Building Department would feel comfortable allowing the temporary use of the ramp
to continue until next yeazs building season if the following requirements were met.
1- In lieu of frost footings, the ramp must be kept level and straight with no more than
1/2"difference were it meets the steps.
2- The ramp is made accessible from the handicap parking stall.
3-A non slip surface is applied to the ramp.